Datasheet

at AC-3 / according to IEC 60947-6-2 /
maximum
at AC-4 / according to IEC 60947-6-2 /
maximum
1/h 300
Control circuit:
Design of activation of the operating mechanism
conventional
Design of the surge suppressor
with diode
Type of voltage / of the controlled supply voltage
DC
Control supply voltage / 1
for DC
rated value
V 24
Working range factor supply voltage rated value / of the
magnet coil
for DC
0.8…1.1
Pull-in power / of the solenoid / for DC
W 4
Holding power / of the solenoid / for DC
W 4
Auxiliary circuit:
Product extension / auxiliary switch
Yes
Contact reliability / of the auxiliary contacts
1 faulty switching per 100 million (17 V, 1 mA)
Number of NC contacts / for auxiliary contacts
instantaneous switching
0
lagging switching
0
Number of NO contacts / for auxiliary contacts
instantaneous switching
1
leading switching
0
Operating current / of the auxiliary contacts
at AC-12 / maximum
A 10
at AC-15
at 230 V
A 10
at 400 V
A 3
at DC-12
at 48 V
A 6
at 60 V
A 6
at 110 V
A 3
at 220 V
A 1
at DC-13
at 24 V
A 6
at 48 V
A 2
at 60 V
A 2
at 110 V
A 1
at 220 V
A 0.3
Short-circuit:
Design of the fuse link
for short-circuit protection of the auxiliary
switch / required
fuse gL/gG: 10 A
for short-circuit protection of the main
circuit
with type of assignment 1 / required
gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED
5SE: 35 A
at type of coordination 2 / required
gL/gG LV HRC 3NA, DIAZED 5SB, NEOZED
5SE: 20A
Installation/mounting/dimensions:
Built in orientation
vertical
Type of mounting
screw and snap-on mounting onto 35 mm