Data Sheet

— up to 400 V for current peak value n=20
rated value
9.6A
— up to 500 V for current peak value n=20
rated value
9.6A
— up to 690 V for current peak value n=20
rated value
8.9A
● at AC-6a
— up to 230 V for current peak value n=30
rated value
6.6A
— up to 400 V for current peak value n=30
rated value
6.4A
— up to 500 V for current peak value n=30
rated value
6.4A
— up to 690 V for current peak value n=30
rated value
6.4A
Minimum cross-section in main circuit
● at maximum AC-1 rated value
4mm²
Operating current for approx. 200000 operating
cycles at AC-4
● at 400 V rated value
5.5A
● at 690 V rated value
4.4A
Operating current
● at 1 current path at DC-1
— at 24 V rated value
20A
— at 110 V rated value
2.1A
— at 220 V rated value
0.8A
— at 440 V rated value
0.6A
— at 600 V rated value
0.6A
● with 2 current paths in series at DC-1
— at 24 V rated value
20A
— at 110 V rated value
12A
— at 220 V rated value
1.6A
— at 440 V rated value
0.8A
— at 600 V rated value
0.7A
● with 3 current paths in series at DC-1
— at 24 V rated value
20A
— at 110 V rated value
20A
— at 220 V rated value
20A
— at 440 V rated value
1.3A
— at 600 V rated value
1A
Operating current
● at 1 current path at DC-3 at DC-5
— at 24 V rated value
20A
3RT2018-1AP01 Subject to change without notice
Page 3/
12
09/11/2019 © Copyright Siemens