Datasheet

— at 110 V rated value
4.5A
— at 220 V rated value
1A
— at 440 V rated value
0.4A
— at 600 V rated value
0.25A
● with 2 current paths in series at DC-1
— at 24 V rated value
35A
— at 110 V rated value
35A
— at 220 V rated value
5A
— at 440 V rated value
1A
— at 600 V rated value
0.8A
● with 3 current paths in series at DC-1
— at 24 V rated value
35A
— at 110 V rated value
35A
— at 220 V rated value
35A
— at 440 V rated value
2.9A
— at 600 V rated value
1.4A
Operating current
● at 1 current path at DC-3 at DC-5
— at 24 V rated value
20A
— at 110 V rated value
2.5A
— at 220 V rated value
1A
— at 440 V rated value
0.09A
— at 600 V rated value
0.06A
● with 2 current paths in series at DC-3 at DC-5
— at 110 V rated value
15A
— at 220 V rated value
3A
— at 24 V rated value
35A
— at 440 V rated value
0.27A
— at 600 V rated value
0.16A
● with 3 current paths in series at DC-3 at DC-5
— at 110 V rated value
35A
— at 220 V rated value
10A
— at 24 V rated value
35A
— at 440 V rated value
0.6A
— at 600 V rated value
0.6A
Operating power
● at AC-1
— at 230 V rated value
13.3kW
— at 230 V at 60 °C rated value
13.3kW
— at 400 V rated value
23kW
— at 400 V at 60 °C rated value
23kW
3RT2023-1AF00 Changes preserved
Page 3/
10
08.04.2016 © Copyright Siemens AG