Datasheet

Residual current of the electronics for control with
signal <0>
● at AC at 230 V maximum permissible
7mA
● at DC at 24 V maximum permissible
16mA
Auxiliary circuit:
Number of NC contacts
● for auxiliary contacts
— instantaneous contact
1
Number of NO contacts
● for auxiliary contacts
— instantaneous contact
1
Operating current at AC-12 maximum 10A
Operating current at AC-15
● at 230 V rated value
10A
● at 400 V rated value
3A
● at 500 V rated value
2A
● at 690 V rated value
1A
Operating current at DC-12
● at 24 V rated value
10A
● at 48 V rated value
6A
● at 60 V rated value
6A
● at 110 V rated value
3A
● at 125 V rated value
2A
● at 220 V rated value
1A
● at 600 V rated value
0.15A
Operating current at DC-13
● at 24 V rated value
10A
● at 48 V rated value
2A
● at 60 V rated value
2A
● at 110 V rated value
1A
● at 125 V rated value
0.9A
● at 220 V rated value
0.3A
● at 600 V rated value
0.1A
Contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings:
Full-load current (FLA) for three-phase AC motor
● at 480 V rated value
21A
● at 600 V rated value
22A
Yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
2hp
3RT2026-1AB00 Changes preserved
Page 5/
10