Datasheet

Operating current
at AC-1 / at 400 V
at 40 °C ambient temperature / rated
value
A 50
at 60 °C ambient temperature / rated
value
A 42
at AC-2 / at 400 V / rated value
A 32
at AC-3 / at 400 V / rated value
A 32
at AC-4 / at 400 V / rated value
A 22
Operating current
with 1 current path / at DC-1
at 24 V / rated value
A 35
at 110 V / rated value
A 4.5
with 2 current paths in series / at DC-1
at 24 V / rated value
A 35
at 110 V / rated value
A 35
with 3 current paths in series / at DC-1
at 24 V / rated value
A 35
at 110 V / rated value
A 35
with 1 current path / at DC-3 / at DC-5
at 24 V / rated value
A 20
at 110 V / rated value
A 2.5
with 2 current paths in series / at DC-3 / at
DC-5
at 24 V / rated value
A 35
at 110 V / rated value
A 15
with 3 current paths in series / at DC-3 / at
DC-5
at 24 V / rated value
A 35
at 110 V / rated value
A 35
Service power
at AC-2 / at 400 V / rated value
kW 15
at AC-3 / at 400 V / rated value
kW 15
at AC-4 / at 400 V / rated value
kW 11
Active power loss / per conductor / typical
W 2.7
Off-load operating frequency
at AC
1/h 5,000
at DC
1/h 1,500
Frequency of operation / at AC-1 / according to IEC
60947-6-2
1/h 1,000
Frequency of operation / at AC-2 / according to IEC
60947-6-2
1/h 750
Frequency of operation / at AC-3 / according to IEC
60947-6-2
1/h 750
Frequency of operation / at AC-4 / according to IEC
60947-6-2
1/h 250
Control circuit:
Type of voltage / of the controlled supply voltage
AC
Control supply voltage / 1
at 50 Hz / for AC / rated value
V 230
at 60 Hz / for AC / rated value
V 230
operating range factor control supply voltage rated
value / of the magnet coil
at 50 Hz / for AC
0.8…1.1
at 60 Hz / for AC
0.85…1.1