Datasheet

for main current circuit
screw-type terminals
for auxiliary and control current circuit
screw-type terminals
Type of the connectable conductor cross-section
for main contacts
solid
2x (1 ... 2.5 mm²), 2x (2.5 ... 10 mm²)
finely stranded
with conductor end processing
2x (1 ... 2.5 mm²), 2x (2.5 ... 6 mm²), 1x 10 mm²
for AWG conductors / for main contacts
2x (16 ... 12), 2x (14 ... 8)
for auxiliary contacts
solid
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
finely stranded
with conductor end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
for AWG conductors / for auxiliary contacts
2x (20 ... 16), 2x (18 ... 14)
Certificates/approvals:
General Product Approval Declaration of Conformity
CCC
CSA
GOST
UL EC-
Declaration of Conformity
Test Certificates
Special Test
Certificate
Type Test
Certificates/Test
Report
Shipping Approval
ABS
(
American Bureau of Shipping
DNV /
Det Norske Veritas
GL /
Germanischer Lloyd
LRS /
Lloyds Register of Shipping
PRS /
Polski Rejestr Statkow
RINA /
Registro Italiano Navale
Shipping
Approval
other
RMRS /
Russian Maritime Register
Confirmation
Household and similar appliances
UL/CSA ratings:
yielded mechanical performance (hp)
for single-phase squirrel cage motors
at 110/120 V / rated value
hp 2
at 230 V / rated value
hp 5
for three-phase squirrel cage motors
at 200/208 V / rated value
hp 10
at 220/230 V / rated value
hp 10
at 460/480 V / rated value
hp 20
at 575/600 V / rated value
hp 25
Operating current (FLA) / for three-phase squirrel cage
motors
at 480 V / rated value
A 27
at 600 V / rated value
A 27
Contact rating designation / for auxiliary contacts /
according to UL
A600 / Q600
Safety:related Parameter:
B10 value / with high demand rate
according to SN 31920
1,000,000
T1 value / for proof test interval or service life
according to IEC 61508
a 20
Proportion of dangerous failures
with low demand rate / according to SN
31920
% 40
with high demand rate / according to SN
% 73
http://support.automation.siemens.com/WW/view/en/33241553&td=1