Data Sheet

— at 110 V rated value
2.5A
— at 220 V rated value
1A
— at 440 V rated value
0.1A
— at 600 V rated value
0.06A
● with 2 current paths in series at DC-3 at DC-5
— at 24 V rated value
55A
— at 110 V rated value
25A
— at 220 V rated value
5A
— at 440 V rated value
0.27A
— at 600 V rated value
0.16A
● with 3 current paths in series at DC-3 at DC-5
— at 24 V rated value
55A
— at 110 V rated value
55A
— at 220 V rated value
25A
— at 440 V rated value
0.6A
— at 600 V rated value
0.35A
Operating power
● at AC-1
— at 230 V rated value
23kW
— at 230 V at 60 °C rated value
21kW
— at 400 V rated value
39kW
— at 400 V at 60 °C rated value
36kW
— at 690 V rated value
68kW
— at 690 V at 60 °C rated value
62kW
● at AC-2 at 400 V rated value
18.5kW
● at AC-3
— at 230 V rated value
11kW
— at 400 V rated value
18.5kW
— at 500 V rated value
22kW
— at 690 V rated value
22kW
Operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value
11.6kW
● at 690 V rated value
16.8kW
Thermal short-time current limited to 10 s 400A
No-load switching frequency
● at AC
50001/h
Operating frequency
● at AC-1 maximum
12001/h
● at AC-2 maximum
7501/h
● at AC-3 maximum
10001/h
3RT2035-1AP00 Subject to change without notice
Page 4/
10
09/11/2019 © Copyright Siemens