Data Sheet

● of contactor typical
10000000
● of the contactor with added auxiliary switch
block typical
100000000
Reference code acc. to DIN EN 81346-2 Q
Ambient conditions
Installation altitude at height above sea level
● maximum
2000m
Relative humidity
● during operation
95%
Main circuit
Number of poles for main current circuit 4
Number of NO contacts for main contacts 4
Operating voltage
● at AC
— at 50 Hz rated value
690V
— at 60 Hz rated value
690V
Operating current
● at AC-1 at 400 V
— at ambient temperature 40 °C rated value
35A
● at AC-1
— up to 690 V at ambient temperature 40 °C
rated value
35A
— up to 690 V at ambient temperature 60 °C
rated value
30A
● at AC-3
— at 400 V rated value
15.5A
● at AC-4 at 400 V rated value
15.5A
Minimum cross-section in main circuit
● at maximum AC-1 rated value
10mm²
Operating power
● at AC-3
— at 400 V rated value
7.5kW
● at AC-4 at 400 V rated value
7.5kW
No-load switching frequency
● at AC
50001/h
Operating frequency
● at AC-1 maximum
10001/h
Control circuit/ Control
Type of voltage AC
Type of voltage of the control supply voltage AC
Control supply voltage at AC
3RT2325-2AP00 Subject to change without notice
Page 2/
9
09/11/2019 © Copyright Siemens