Data Sheet

● for live parts
— forwards
10mm
— upwards
10mm
— downwards
10mm
— at the side
6mm
Connections/ Terminals
Type of electrical connection
● for main current circuit
spring-loaded terminals
● for auxiliary and control current circuit
spring-loaded terminals
Type of connectable conductor cross-sections
● for main contacts
— solid
2x (1 ... 10 mm²)
— single or multi-stranded
2x (1 ... 10 mm²)
— finely stranded with core end processing
2x (1 ... 6 mm²)
— finely stranded without core end
processing
2x (1 ... 6 mm²)
● at AWG conductors for main contacts
2x (18 ... 8)
Connectable conductor cross-section for main
contacts
● solid
1...10mm²
● single or multi-stranded
1...10mm²
● stranded
1...10mm²
● finely stranded with core end processing
1...6mm²
● finely stranded without core end processing
1...6mm²
Connectable conductor cross-section for auxiliary
contacts
● single or multi-stranded
0.5...2.5mm²
● finely stranded with core end processing
0.5...1.5mm²
● finely stranded without core end processing
0.5...2.5mm²
Type of connectable conductor cross-sections
● for auxiliary contacts
— solid
2x (0.5 ... 2.5 mm²)
— single or multi-stranded
2x (0,5 ... 2,5 mm²)
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²)
— finely stranded without core end
processing
2x (0.5 ... 2.5 mm²)
● at AWG conductors for auxiliary contacts
2x (20 ... 14)
AWG number as coded connectable conductor cross
section
● for main contacts
18...8
● for auxiliary contacts
20...14
Safety related data
3RT2325-2AP00 Subject to change without notice
Page 5/
9
09/11/2019 © Copyright Siemens