Datasheet

— at 24 V rated value
20A
— at 110 V rated value
12A
— at 220 V rated value
1.6A
— at 440 V rated value
0.8A
Operating current
● at 1 current path at DC-3 at DC-5
— at 24 V per NC contact rated value
20A
— at 24 V per NO contact rated value
20A
— at 110 V per NC contact rated value
0.075A
— at 110 V per NO contact rated value
0.15A
— at 220 V per NC contact rated value
0.375A
— at 220 V per NO contact rated value
0.75A
● with 2 current paths in series at DC-3 at DC-5
— at 24 V per NC contact rated value
20A
— at 24 V per NO contact rated value
20A
— at 110 V per NC contact rated value
0.175A
— at 110 V per NO contact rated value
0.35A
Operating power
● at AC-1
— at 230 V rated value
7.5kW
— at 400 V rated value
13kW
● at AC-2 at AC-3
— at 230 V per NC contact rated value
2.2kW
— at 230 V per NO contact rated value
3kW
— at 400 V per NC contact rated value
4kW
— at 400 V per NO contact rated value
5.5kW
Power loss [W] at AC-3 at 400 V for rated value of
the operating current per conductor
1.2W
No-load switching frequency
● at AC
100001/h
● at DC
100001/h
Operating frequency
● at AC-1 maximum
10001/h
Control circuit/ Control
Type of voltage of the control supply voltage AC
Control supply voltage at AC
● at 50 Hz rated value
230V
● at 60 Hz rated value
230V
Operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz
0.8...1.1
3RT2517-1AP00 Subject to change without notice
Page 3/
10
08/21/2019 © Copyright Siemens