5.10 Technical data
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
541
Type 3RU21 16 3RU21 26
Size S00 S0
Width 45 mm 45 mm
Current setting A 0.11 to 0.16 to
11 to 16
1.8 to 2.5 to
34 to 40
Power loss per device (max.) W 3.9 ... 6.6 3.9 ... 6
Short-circuit protection
With fuse without contactor
See "Selection and ordering data" in Catalog
LV 1 N SIRIUS Innovations
With fuse and contactor
See the chapter titled "Motor starter protectors (Page 379)"
Protective separation between main and
auxiliary courrent paths
acc. to IEC/EN 60947-1
V 440
5.10.2.3 Conductor cross-sections main circuit
Table 5- 40 Technical data for the main circuit connection, 3RU21 overload relays
Type 3RU21 16 3RU21 26
Size S00 S0
Width 45 mm 45 mm
Connection type Screw connection
Connection screw
M3, Pozidriv size 2 M4, Pozidriv size 2
Operating tool
∅ 5 to 6 ∅ 5 to 6
Tightening torque
Nm 0.8 to 1.2 2 to 2.5
Conductor cross-sections (min./max.), 1-wire or 2-wire connection possible
- Solid mm
2
2 x (0.5 to 1.5)
1)
; 2 x (0.75 to 2.5)
1)
2 x (0.5 to 4)
1)
2 x (1 to 2.5)
1)
2 x (2.5 to 10)
1)
- Finely stranded with end sleeve
(DIN 46228 Part 1)
mm
2
2 x (0.5 to 1.5)
1)
2 x (0.75 to 2.5)
2)
2 x (1 to 2.5)
1)
; 2 x (2.5 to 6)
1)
; max. 1 x 10
- AWG cables, solid or stranded AWG 2 x (20 to 16)
1)
; 2 x (18 to 14)
1)
2 x 12
2 x (16 to 12)
1)
2 x (14 to 8)
1)
Connection type Spring-loaded connection
Operating tool
∅ 3.0 x 0.5 ∅ 3.5 x 0.5
Conductor cross-sections (min./max.)
- Solid mm
2
1 x (0.5 to 4) 1 x (1 to 10)
- Finely stranded without end sleeve mm
2
1 x (0.5 to 2.5) 1 x (1 to 6)
- Finely stranded with end sleeve
(DIN 46228 Part 1)
mm
2
1 x (0.5 to 2.5) 1 x (1 to 6)
- AWG cables, solid or stranded AWG 1 x (20 to 12) 1 x (18 to 8)