User Manual

SIRIUS 3RU2/3RB3 overload relays
5.10 Technical data
SIRIUS Innovations
System Manual, 01/2011, A8E56203870002-03
549
5.10.3.3 Conductor cross-sections main circuit
Table 5- 45 Technical data for the main circuit connection, 3RB30/3RB31 overload relays
Type 3RB30 1.,
3RB31 1.
3RB30 2.,
3RB31 2.
Size S00 S0
Width 45 mm 45 mm
Connection type Screw terminals with box terminal
Connection screw
M3, Pozidriv size 2 M4, Pozidriv size 2
Operating tool
∅ 5 to 6 ∅ 5 to 6
Tightening torque
Nm 0.8 to 1.2 2 to 2.5
Conductor cross-sections (min./max.), 1-wire or 2-wire
- Solid mm
2
2 x (0.5 to 1.5)
1)
; 2 x (0.75 to 2.5)
1)
2 x (0.5 to 4)
1)
2 x (1 to 2.5)
1)
2 x (2.5 to 10)
1)
- Finely stranded with end
sleeve
mm
2
2 x (0.5 to 1.5)
1)
2 x (0.75 to 2.5)
1)
2 x (1 to 2.5)
1)
; 2 x (2.5 to 6)
1)
; max. 1 x 10
- AWG cables, solid or stranded AWG 2 x (20 to 16)
1)
2 x (18 to 14)
1)
2 x 12
1)
2 x (16 to 12)
1)
2 x (14 to 8)
1)
Connection type Spring-loaded connection
Operating tool
∅ 3.0 x 0.5 and ∅ 3.5 x 0.5
Conductor cross-sections (min./max.)
- Solid mm
2
1 x (0.5 to 4) 1 x (1 to 10)
- Finely stranded without end
sleeve
mm
2
1 x (0.5 to 2.5) 1 x (1 to 6)
- Finely stranded with end
sleeve (DIN 46228 Part 1)
mm
2
1 x (0.5 to 2.5) 1 x (1 to 6)
- AWG cables, solid or
stranded
AWG 1 x (20 to 12) 1 x (18 to 8)
1)
If two different conductor cross-sections are being connected to one clamping point, both cross-sections must be
located in the range indicated. If identical cross-sections are used, this restriction does not apply.