Datasheet

● on the front
IP20
● of the terminal
IP00
Shock resistance
● acc. to IEC 60068-2-27
8g / 11 ms
Recovery time
● after overload trip with automatic reset typical
10min
● after overload trip with remote-reset
10min
● after overload trip with manual reset
10min
Type of protection according to ATEX directive
2014/34/EU
Ex II (2) GD
Certificate of suitability according to ATEX directive
2014/34/EU
DMT 98 ATEX G 001
Protection against electrical shock finger-safe when touched vertically from front acc. to IEC 60529
Reference code acc. to DIN EN 81346-2 F
Ambient conditions
Installation altitude at height above sea level
● maximum
2000m
Ambient temperature
● during operation
-40...+70°C
● during storage
-55...+80°C
● during transport
-55...+80°C
Temperature compensation -40...+60°C
Relative humidity during operation 0...90%
Main circuit
Number of poles for main current circuit 3
Adjustable pick-up value current of the current-
dependent overload release
22...32A
Operating voltage
● rated value
690V
● at AC-3 rated value maximum
690V
Operating frequency rated value 50...60Hz
Operating current rated value 32A
Auxiliary circuit
Design of the auxiliary switch integrated
Number of NC contacts for auxiliary contacts 1
● Note
for contactor disconnection
Number of NO contacts for auxiliary contacts 1
● Note
for message "Tripped"
Number of CO contacts
● for auxiliary contacts
0
Operating current of auxiliary contacts at AC-15
● at 24 V
3A
3RU2136-4EB0 Subject to change without notice
Page 2/
7
08/20/2019 © Copyright Siemens