Datasheet
● for auxiliary contacts
0
Protective and monitoring functions
Trip class CLASS 10
Design of the overload release thermal
Operational short-circuit current breaking capacity
(Ics) at AC
● at 240 V rated value
100000A
● at 400 V rated value
100000A
● at 500 V rated value
100000A
● at 690 V rated value
100000A
Maximum short-circuit current breaking capacity (Icu)
● at AC at 240 V rated value
100kA
● at AC at 400 V rated value
100kA
● at AC at 500 V rated value
100kA
● at AC at 690 V rated value
100kA
Breaking capacity short-circuit current (Icn)
● at 1 current path at DC at 150 V rated value
10kA
● with 2 current paths in series at DC at 300 V
rated value
10kA
● with 3 current paths in series at DC at 450 V
rated value
10kA
UL/CSA ratings
Full-load current (FLA) for three-phase AC motor
● at 480 V rated value
0.16A
● at 600 V rated value
0.16A
Short-circuit protection
Product function Short circuit protection Yes
Design of the short-circuit trip magnetic
Design of the fuse link for IT network for short-circuit
protection of the main circuit
● at 240 V
none required
● at 400 V
None required
● at 500 V
None required
● at 690 V
None required
Installation/ mounting/ dimensions
Mounting position any
Mounting type screw and snap-on mounting onto 35 mm standard mounting rail
according to DIN EN 60715
Height 90mm
Width 45mm
Depth 81mm
3RV1011-0AA10 Subject to change without notice
Page 3/
6
02/09/2017 © Copyright Siemens AG