Datasheet

Shock resistance
● acc. to IEC 60068-2-27
25g / 11 ms
Mechanical service life (switching cycles)
● of the main contacts typical
100000
● of auxiliary contacts typical
100000
Electrical endurance (switching cycles)
● typical
100000
Type of protection Increased safety
Certificate of suitability relating to ATEX on request
Protection against electrical shock finger-safe
Equipment marking acc. to DIN EN 81346-2 Q
Ambient conditions:
Installation altitude at height above sea level
maximum
2000m
Ambient temperature
● during operation
-20...+60°C
● during storage
-50...+80°C
● during transport
-50...+80°C
Temperature compensation -20...+60°C
Relative humidity during operation 10...95%
Main circuit:
Number of poles for main current circuit 3
Adjustable pick-up value current of the current-
dependent overload release
0.14...0.2A
Operating voltage
● rated value
690V
● at AC-3 rated value maximum
690V
Operating frequency rated value 50...60Hz
Operating current rated value 0.2A
Operating current
● at AC-3
— at 400 V rated value
0.2A
Operating power
● at AC-3
— at 230 V rated value
30W
— at 400 V rated value
60W
— at 500 V rated value
60W
— at 690 V rated value
90W
Operating frequency
● at AC-3 maximum
151/h
Auxiliary circuit:
3RV2011-0BA10 Changes preserved
Page 2/
7
26.02.2016 © Copyright Siemens AG