Datasheet
Short-circuit:
Breaking capacity limit short-circuit current (lcu)
• at 400 V / rated value A 100,000
• at 500 V / rated value A 100,000
• at 690 V / rated value A 100,000
Design of the overcurrent release and short-circuit release thermomagnetic
Installation/mounting/dimensions:
Built in orientation any
Type of mounting screw and snap-on mounting onto 35 mm standard
mounting rail according to DIN EN 60715
Width mm 45
Height mm 97
Depth mm 91
Distance, to be maintained, to the ranks assembly
• forwards mm 0
• backwards mm 0
• upwards mm 50
• downwards mm 50
• sidewards mm 0
Distance, to be maintained, to earthed part
• forwards mm 0
• backwards mm 0
• upwards mm 50
• sidewards mm 30
• downwards mm 50
Distance, to be maintained, conductive elements
• forwards mm 0
• backwards mm 0
• upwards mm 50
• downwards mm 50
• sidewards mm 30
Connections:
Product function
• removable terminal for main circuit No
• removable terminal for auxiliary and control circuit No
Design of the electrical connection
• for main current circuit screw-type terminals
Type of the connectable conductor cross-section
• for main contacts
3RV2011-0KA10
Page 3/ 03/30/2012
subject to modifications
© Copyright Siemens AG 2012