Datasheet
● Rated value
690V
● at AC-3 Rated value maximum
690V
Operating frequency Rated value 50...60Hz
Operating current Rated value 1.25A
Operating current
● at AC-3
— at 400 V Rated value
1.25A
Operating frequency
● at AC-3 maximum
151/h
Auxiliary circuit:
Number of NC contacts
● for auxiliary contacts
0
Number of NO contacts
● for auxiliary contacts
0
Number of CO contacts
● for auxiliary contacts
0
Product expansion Auxiliary switch Yes
Protective and monitoring functions:
Trip class CLASS 10
Design of the overload circuit breaker thermal
Operational short-circuit current breaking capacity
(Ics) with AC
● at 240 V Rated value
100kA
● at 400 V Rated value
100kA
● at 500 V Rated value
100kA
● at 690 V Rated value
100kA
Maximum short-circuit current breaking capacity (Icu)
● with AC at 240 V Rated value
100kA
● with AC at 400 V Rated value
100kA
● with AC at 500 V Rated value
100kA
● with AC at 690 V Rated value
100kA
Breaking capacity short-circuit current (Icn)
● with 1 current path for DC at 150 V Rated value
10kA
● with 2 current paths in series for DC at 300 V
Rated value
10kA
● with 3 current paths in series for DC at 450 V
Rated value
10kA
Response value current of the instantaneous short-
circuit release
16A
UL/CSA ratings:
Full-load current (FLA) for three-phase AC motor
● at 480 V Rated value
1.25A
3RV2011-0KA10 Changes preserved
Page 2/
7
19.05.2015 © Copyright Siemens AG