Datasheet
Type of connectable conductor cross-section
● for main contacts
— single or multi-stranded
2x (0,75 ... 2,5 mm²), 2x 4 mm²
— finely stranded with core end processing
2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● for AWG conductors for main contacts
2x (18 ... 14), 2x 12
Design of screwdriver shaft Diameter 5 to 6 mm
Design of the thread of the connection screw
● for main contacts
M3
Safety related data:
B10 value with high demand rate acc. to SN 31920 50000
Proportion of dangerous failures
● with low demand rate acc. to SN 31920
40%
● with high demand rate acc. to SN 31920
40%
T1 value for proof test interval or service life acc. to
IEC 61508
10y
Protection against electrical shock finger-safe
Mechanical data:
Size of the circuit-breaker S00
Ambient conditions:
Installation altitude at height above sea level
maximum
2000m
Ambient temperature
● during operation
-20...+60°C
● during storage
-50...+80°C
● during transport
-50...+80°C
Relative humidity during operation 10...95%
Display:
Display version
● for switching status
Handle
Certificates/ approvals:
3RV2011-0KA10 Changes preserved
Page 4/
7
19.05.2015 © Copyright Siemens AG