Data Sheet

Operating frequency
● at AC-3 maximum
151/h
Auxiliary circuit
Number of NC contacts for auxiliary contacts 0
Number of NO contacts for auxiliary contacts 0
Number of CO contacts
● for auxiliary contacts
0
Protective and monitoring functions
Product function
● Ground fault detection
No
● Phase failure detection
Yes
Trip class CLASS 10
Design of the overload release thermal
Operational short-circuit current breaking capacity
(Ics) at AC
● at 240 V rated value
100kA
● at 400 V rated value
100kA
● at 500 V rated value
42kA
● at 690 V rated value
4kA
Maximum short-circuit current breaking capacity (Icu)
● at AC at 240 V rated value
100kA
● at AC at 400 V rated value
100kA
● at AC at 500 V rated value
42kA
● at AC at 690 V rated value
6kA
Response value current
● of instantaneous short-circuit trip unit
130A
UL/CSA ratings
Full-load current (FLA) for three-phase AC motor
● at 480 V rated value
10A
● at 600 V rated value
10A
Yielded mechanical performance [hp]
● for single-phase AC motor
— at 110/120 V rated value
0.5hp
— at 230 V rated value
1.5hp
● for three-phase AC motor
— at 200/208 V rated value
2hp
— at 220/230 V rated value
3hp
— at 460/480 V rated value
5hp
— at 575/600 V rated value
7.5hp
Short-circuit protection
3RV2011-1JA40 Subject to change without notice