Datasheet

phase disturbance recognition
Yes
Product component
auxiliary switch
No
undervoltage release mechanism
No
trip indicator
No
Product extension / optional / motor drive
No
Main circuit:
Number of poles / for main current circuit
3
Operating voltage / at AC-3 / rated value / maximum
V 690
Operating current / at AC-3 / at 400 V / rated value
A 28
Service power / at AC-3
at 400 V / rated value
W 11,000
at 500 V / rated value
W 18,500
at 690 V / rated value
W 22,000
Frequency of operation / at AC-3 / according to IEC
60947-6-2 / maximum
1/h 15
Arrangement of electrical connectors / for main current
circuit
Top and bottom
Adjustable response current
of the non-delayed short-circuit release
A 364…364
of the current-dependent overload release
A 23…28
Service power / at AC-3 / at 230 V / rated value
W 7,500
Continuous current / rated value
A 28
Auxiliary circuit:
Product extension / auxiliary switch
Yes
Number of NC contacts / for auxiliary contacts /
instantaneous switching
0
Number of NO contacts / for auxiliary contacts /
instantaneous switching
0
Number of change-over switches / for auxiliary contacts
0
Inputs/ Outputs:
Number of digital inputs
0
Short-circuit:
Breaking capacity limit short-circuit current (lcu)
at 400 V / rated value
A 55,000
at 500 V / rated value
A 10,000
at 690 V / rated value
A 4,000
Design of the overcurrent release and short-circuit
release
thermomagnetic
Installation/mounting/dimensions:
Built in orientation
any
Type of mounting
screw and snap-on mounting onto 35 mm
standard mounting rail according to DIN EN
60715
Width
mm 45
Height
mm 97
Depth
mm 91
Distance, to be maintained, to the ranks assembly
forwards
mm 0
backwards
mm 0
upwards
mm 50
downwards
mm 50
sidewards
mm 0
Distance, to be maintained, to earthed part
forwards
mm 0
mm 0
http://support.automation.siemens.com/WW/view/en/33244368&td=1
Page 2 of 6 3/30/2012 1:39:24 PM