Datasheet

Operating current
● at 40 °C rated value
A 80
● at 50 °C rated value
A 73
● at 60 °C rated value
A 66
Mechanical power output for three-phase motors
● at 230 V
— at standard circuit at 40 °C rated value
W 22000
● at 400 V
— at standard circuit at 40 °C rated value
W 45000
Yielded mechanical performance [hp] for three-phase
AC motor at 200/208 V at standard circuit at 50 °C
rated value
hp 20
Operating frequency rated value Hz 50...60
Relative negative tolerance of the operating
frequency
% -10
Relative positive tolerance of the operating frequency % 10
Operating voltage at standard circuit rated value V 200...480
Relative negative tolerance of the operating voltage
at standard circuit
% -15
Relative positive tolerance of the operating voltage at
standard circuit
% 10
Minimum load [%] % 20
Adjustable motor current for motor overload
protection minimum rated value
A 43
Continuous operating current [% of Ie] at 40 °C % 115
Power loss [W] at operating current at 40 °C during
operation typical
W 12
Control electronics
Type of voltage of the control supply voltage AC/DC
Control supply voltage frequency 1 rated value Hz 50
Control supply voltage frequency 2 rated value Hz 60
Relative negative tolerance of the control supply
voltage frequency
% -10
Relative positive tolerance of the control supply
voltage frequency
% 10
Control supply voltage 1 at AC
● at 50 Hz rated value
V 24
● at 60 Hz rated value
V 24
Relative negative tolerance of the control supply
voltage at AC at 60 Hz
% -20
Relative positive tolerance of the control supply
voltage at AC at 60 Hz
% 20
Control supply voltage 1 at DC rated value V 24
3RW40 46-1BB04 Subject to change without notice
Page 2/
7
12/14/2018 © Copyright Siemens