Datasheet

● of full range R fuse link for semiconductor
protection usable up to 690 V
3NE1815-0; Type of coordination 2, Iq = 65 kA
● of back-up R fuse link for semiconductor
protection usable up to 690 V
3NE8017-1; Type of coordination 2, Iq = 65 kA
General technical data
Starting voltage [%] 30...100%
Start-up ramp time of soft starter 0...20s
Current limiting value [%] adjustable 130...700%
Product component
● is supported HMI-Standard
Yes
● is supported HMI-High Feature
Yes
Product feature integrated bypass contact system Yes
Number of controlled phases 3
Trip class CLASS 10A (default) / 10E / 20E; acc. to IEC 60947-4-2
Insulation voltage
● rated value
600V
Impulse voltage rated value 6kV
Blocking voltage of the thyristor maximum 1600V
Service factor 1
Surge voltage resistance rated value 6kV
maximum permissible voltage for safe isolation
● between main and auxiliary circuit
600V
Protection class IP IP20
Usage category acc. to IEC 60947-4-2 AC 53a
Shock resistance 15 g / 11 ms, from 12 g / 11 ms with potential contact lifting
Reference code acc. to DIN EN 81346-2 Q
Product function
● ramp-up (soft starting)
Yes
● ramp-down (soft stop)
Yes
● Soft Torque
Yes
● Adjustable current limitation
Yes
● pump ramp down
Yes
● Intrinsic device protection
Yes
● motor overload protection
Yes; Electronic motor overload protection
● Evaluation of thermistor motor protection
No
● inside-delta circuit
Yes
● Auto-reset
Yes
● Manual RESET
Yes
● remote reset
Yes; By turning off the control supply voltage
● communication function
Yes
● via software configurable
Yes