Datasheet

● during operation acc. to IEC 60721
3K6 (no ice formation, only occasional condensation), 3C3 (no
salt mist), 3S2 (sand must not get into the devices), 3M6
● during storage acc. to IEC 60721
1K6 (only occasional condensation), 1C2 (no salt mist), 1S2 (sand
must not get inside the devices), 1M4
● during transport acc. to IEC 60721
2K2, 2C1, 2S1, 2M2 (max. fall height 0.3 m)
Communication/ Protocol
Communication module is supported
● PROFINET standard
Yes
● Modbus TCP
Yes
● PROFIBUS
Yes
UL/CSA ratings
Manufacturer's article number
● of fuse
— at Standard Faults usable up to 575/600 V
according to UL
Type: Class RK5 / K5, max. 50 A; Iq = 5 kA
— at High Faults usable up to 575/600 V
according to UL
Type: Class J / L, max. 50 A; Iq = 100 kA
— at Standard Faults usable at inside-delta
circuit up to 575/600 V according to UL
Type: Class RK5 / K5, max. 50 A; Iq = 5 kA
— at High Faults usable at inside-delta circuit
up to 575/600 V according to UL
Type: Class J / L, max. 50 A; Iq = 100 kA
Operating power [hp] for three-phase motors
● at 200/208 V at 50 °C rated value
2hp
● at 220/230 V at 50 °C rated value
3hp
● at 460/480 V at 50 °C rated value
7.5hp
● at 200/208 V at inside-delta circuit at 50 °C
rated value
5hp
● at 220/230 V at inside-delta circuit at 50 °C
rated value
5hp
● at 460/480 V at inside-delta circuit at 50 °C
rated value
10hp
Contact rating of auxiliary contacts according to UL R300-B300
3RW5213-1AC04 Subject to change without notice
Page 6/
10
06/04/2019 © Copyright Siemens