Data Sheet
● typical
10000000
Electrical endurance (switching cycles)
● at AC-15 at 230 V typical
100000
Electrical endurance (switching cycles) with contactor
3RH11, 3RT1016, 3RT1017, 3RT1024, 3RT1025,
3RT1026 typical
10000000
Electrical operating cycles in one hour with contactor
3RH11, 3RT1016, 3RT1017, 3RT1024, 3RT1025,
3RT1026
6000
Thermal current 10A
Material of the enclosure of the switch head plastic
Reference code acc. to DIN EN 81346-2 B
Reference code acc. to DIN EN 61346-2 B
Continuous current of the C characteristic MCB 1A; for a short-circuit current smaller than 400 A
Continuous current of the quick DIAZED fuse link 10A; for a short-circuit current smaller than 400 A
Continuous current of the DIAZED fuse link gG 6A
Active principle mechanical
Repeat accuracy 0.05mm
Minimum actuating torque in activation direction 0.25N·m
Length of the sensor 220.3mm
Width of the sensor 40mm
Design of the switching contact mechanical
Operating frequency rated value 50...60Hz
Number of NC contacts for auxiliary contacts 2
Number of NO contacts for auxiliary contacts 1
Number of CO contacts for auxiliary contacts 1
Operating current at AC-15
● at 24 V rated value
6A
● at 125 V rated value
6A
● at 240 V rated value
6A
● at 400 V rated value
4A
Operating current at DC-13
● at 24 V rated value
3A
● at 125 V rated value
0.55A
● at 250 V rated value
0.27A
● at 400 V rated value
0.12A
Design of the interface for safety-related
communication
without
Enclosure
Design of the housing block, narrow
Material of the enclosure plastic
Coating of the enclosure Other types
Design of the housing acc. to standard Yes
3SE5132-0LR01 Subject to change without notice
Page 2/
6
09/13/2019 © Copyright Siemens