SIRIUS ACT 3SU1 pushbuttons and signaling devices
226 System Manual, 02/2015, A5E03457306020A/RS-AB/002
10.2.5
Diagnostics
10.2.5.1
IO-Link diagnostics
IO-Link diagnostics
On the electronic modules for ID key-operated switches for IO-Link, it is possible to carry out
diagnostics via IO-Link. Short-circuit is signaled via the diagnostics mechanism of IO-Link.
With all further diagnostics messages, the corresponding bit is set in data set (index) 92 -
diagnostics.
The table below provides information on possible causes and remedial measures:
Table 10- 6 Possible causes and remedial measures
Diagnostics and messages
Possible cause
Possible remedial measures
Short-circuit
The electrical cable connection on at
least one of the digital outputs has been
short-circuited.
The connected actuator is defective.
The current consumption of the con-
nected actuator is too high.
Check the electrical cable con-
nection of the digital outputs.
Check the current consumption of
the connected actuator.
Use a new actuator.
Self-test error / internal error
Fault in internal test.
The data saved in the device are inva-
lid.
Reset the electronic module to
the delivery state and reconfigure
the electronic module.
Return the device to the manufac-
turer.
Individually encodable ID key cannot
be saved:
Key list is full
50 individually encodable keys have al-
ready been saved, and the available
memory range is full.
Check the data in data sets 81
and 82 (memory of the individual-
ly encodable ID keys (1-30) - data
set (index) 81, and memory of the
individually encodable ID keys
(31-50) - data set (index) 82)
Delete the no longer used individ-
ually encodable ID keys from the
memory.
Individually encodable ID key cannot
be saved:
invalid key
No valid individually encodable ID key
inserted.
The inserted individually encodable
ID key is defective.
Use an individually encodable
ID key if, for example, a colored
ID key has been inserted.
Use another individually en-
codable ID key since the inserted
ID key could be defective.
Check that the ID key has been
inserted as far as it will go.