User Manual

IO-Link
10.2 Design of a command point with ID key-operated switch
SIRIUS ACT 3SU1 pushbuttons and signaling devices
System Manual, 02/2015, A5E03457306020A/RS-AB/002
229
10.2.6
Connecting
10.2.6.1
Electronic modules for the ID key-operated switches for IO-Link
3SU1400-1GD10-1AA0 electronic module for ID key-operated switches for IO-Link
Terminal labeling
The IO-Link device is connected to the IO-Link master via the terminals L+, C/Q and L-. The
IO-Link device is powered (24 V DC) via the two cables L+ and L-. Communication of the
IO-Link device with the IO-Link master takes place via the cable C/Q. The current available
at one IO-Link port of the IO-Link master is 200 mA. If more than 200 mA are required for the
IO-Link device, the terminals 1M and 1L+ can be additionally connected.
Terminal labeling
Pin
X1
Pin
X2
1
DQ.0
Digital output
6
L+
Supply voltage for IO-Link
2
DQ.1
Digital output
7
C/Q
Communication signal/switching signal
3
DQ.2 Digital output
8
L- IO-Link ground
4
DQ.3
Digital output
9
1M
Ground
5
DO.4
Digital output
10
1L+
24 V DC