Information

13/16
Siemens IC 10 · 2018
SIRIUS ACT Pushbuttons and Indicator Lights
General data
13
Technical specifications
More information
Industry Mall, see www.siemens.com/product?3SU1 Configurator, see www.siemens.com/sirius-act/configurator
Conversion tool, see www.siemens.com/sirius/conversion-tool
Manual, see https://support.industry.siemens.com/cs/ww/en/view/107542462
Type 3SU1..0-.AA
3SU1..0-.JA
3SU1..1-.AA
3SU1..1-.JA
3SU1..0-.AB
3SU1..0-.BB
3SU1..0-.CB
3SU1..0-.DB
3SU1..0-.JB
3SU1..1-.AB
3SU1..1-.BB
3SU1..1-.JB
Product version
Pushbuttons
Operating principle of the actuating element Latching Momentary contact
Optional expansion of product
by light source
No Yes No Yes
Mechanical endurance (operating cycles)
typical
500 000 10 000 000 3 000 000
Switching frequency maximum 1/h
1 800 3600
Shock resistance acc. to IEC 60068-2-27 Half-sine wave 50 g/11 ms
Vibration resistance acc. to IEC 60068-2-6
10 ... 500 Hz: 5 g
Degree of protection
IP66, IP67, IP69 (IP69K)
Environmental category during operation
According to IEC 60721
3M6, 3S2, 3B2, 3C3, 3K6 (with a relative air humidity of 10 ... 95%)
Ambient temperature
During operation °C -25 +70
During storage °C
-40 +80
Type 3SU1.00-.AA
3SU1.00-.BA
3SU1.00-.CA
3SU1.30-.AA
3SU1.30-.BA
3SU1.50-.AA
3SU1.50-.BA
3SU1.50-.CA
3SU1.50-.EA 3SU1.01-.AA
3SU1.01-.BA
3SU1.51-.AA
3SU1.51-.BA
3SU1.51-.CA
3SU1.00-.AD
3SU1.00-.BD
3SU1.00-.CD
3SU1.30-.AD
3SU1.30-.BD
3SU1.50-.AD
3SU1.50-.BD
3SU1.50-.CD
3SU1.50-.ED 3SU1.01-.AD
3SU1.01-.BD
3SU1.31-.AD
3SU1.31-.BD
Product version
Mushroom pushbuttons
Operating principle of the actuating element Latching Momentary
contact
Optional expansion of product
by light source
No Yes No Yes
Mechanical endurance (operating cycles)
typical
500 000 300 000 500 000 10 000 000 300 000 3 000 000
Switching frequency maximum 1/h
1 800 3 600 1 800 3600
Shock resistance acc. to IEC 60068-2-27
Half-sine wave 50 g/11 ms
Vibration resistance acc. to IEC 60068-2-6 10 ... 500 Hz: 5 g
Degree of protection IP66, IP67, IP69
(IP69K)
IP65, IP67, IP69
(IP69K)
IP66, IP67, IP69 (IP69K) IP65, IP67, IP69
(IP69K)
IP66, IP67, IP69
(IP69K)
Environmental category during operation
According to IEC 60721
3M6, 3S2, 3B2, 3C3, 3K6 (with a relative air humidity of 10 ... 95%)
Ambient temperature
During operation °C -25 +70
During storage °C
-40 +80
Type 3SU1...-.J
3SU1...-.H
3SU1...-.G
Product version
EMERGENCY STOP mushroom push-
buttons
Mechanical endurance (operating cycles) 300 000
Switching frequency maximum 1/h 600
Shock resistance acc. to IEC 60068-2-27 Half-sine wave 50 g/11 ms
Vibration resistance acc. to IEC 60068-2-6 10 ... 500 Hz: 5 g
Degree of protection IP66, IP67, IP69 (IP69K)
Environmental category during operation
According to IEC 60721
3M6, 3S2, 3B2, 3C3, 3K6 (with a relative air humidity of 10 ... 95 %)
Ambient temperature
During operation °C -25 ... +70
During storage °C -40 ... +80
© Siemens AG 2017