Datasheet

Continuous current of the DIAZED fuse link gG 10A
Operating voltage
● at AC
— at 50 Hz rated value
5...500V
— at 60 Hz rated value
5...500V
● at DC
— rated value
5...500V
Power Electronics
Contact reliability One maloperation per 100 million (17 V, 5 mA), one maloperation
per 10 million (5 V, 1 mA)
Auxiliary circuit
Design of the contact of auxiliary contacts Silver alloy
Number of NC contacts for auxiliary contacts 1
Number of NO contacts for auxiliary contacts 1
Number of CO contacts
● for auxiliary contacts
0
Connections/Terminals
Type of electrical connection
● of modules and accessories
Screw-type terminal
Type of connectable conductor cross-sections
● solid with core end processing
2x (0.5 ... 0.75 mm²)
● solid without core end processing
2x (1.0 ... 1.5 mm²)
● finely stranded with core end processing
2x (0.5 ... 1.5 mm²)
● finely stranded without core end processing
2x (1,0 ... 1,5 mm²)
● at AWG conductors
2x (18 ... 14)
Tightening torque of the screws in the bracket 1...1.2N·m
Tightening torque
● with screw-type terminals
0.8...0.9N·m
Safety related data
B10 value
● with high demand rate acc. to SN 31920
100000
Proportion of dangerous failures
● with low demand rate acc. to SN 31920
20%
● with high demand rate acc. to SN 31920
20%
Failure rate [FIT]
● with low demand rate acc. to SN 31920
100FIT
T1 value for proof test interval or service life acc. to
IEC 61508
20y
Ambient conditions
Ambient temperature
3SU1130-2BF60-1MA0 Subject to change without notice
Page 3/
6
05/31/2019 © Copyright Siemens