User Manual

3SU14 modules
7.3 Connecting
SIRIUS ACT 3SU1 pushbuttons and signaling devices
144 System Manual, 02/2015, A5E03457306020A/RS-AB/002
7.3
Connecting
Procedure for wiring a screw terminal
Insert the relevant cable into the opening of the screw terminal of the module until it engages.
Insert the screwdriver (DIN ISO 8764-1-PZD1) at an angle of 10° into the opening for the
screw.
Tighten the screw.
Tightening torque for contact modules: 0.8 0.9 Nm
Tightening torque for LED modules: 0.81.0 Nm
Pull on the cable to ensure it is screwed tight.
Procedure for wiring a spring-loaded terminal
Insert the screwdriver (3RA2908-1A: 3.0 mm x 0.5 mm) into the rectangular opening to open
the terminal (round opening).
Insert the cable as far as it will go into the round opening
Remove the screwdriver.
Pull on the cable to ensure it is tight.