User Manual

AS-Interface
9.7 Configuring the AS-Interface
SIRIUS ACT 3SU1 pushbuttons and signaling devices
System Manual, 02/2015, A5E03457306020A/RS-AB/002
195
9.7.3
Addressing the AS-Interface modules for base mounting
To address the AS-Interface modules for base mounting, connect the
3RK1904-2AB02 AS-Interface addressing unit.
3SU1400-2EK10-6AA0
and
3SU1400-2EJ10-6AA0
AS-Interface modules
Technical data
3SU1400-2EK10-6AA0
3SU1400-2EJ10-6AA0
I
e
< 260 mA
U
e
18.0 V ... 31.6 V
AS-i slave profile IO / ID / ID2
(HEX)
7 / 0 / E 7 / A / E
ID1 code (HEX)
1 ... F
1 ... F