User Manual

IO-Link
10.2 Design of a command point with ID key-operated switch
SIRIUS ACT 3SU1 pushbuttons and signaling devices
220 System Manual, 02/2015, A5E03457306020A/RS-AB/002
10.2.3.6
"Switch position delay" parameter
Switch position delay
The switch position delay specifies how long a temporary key position is displayed at the ID
key-operated switch (by green flashing of the LED on the electronic module for ID key-
operated switches). During this time, it is still possible to change the temporary key position
by turning the knob. The switch position delay restarts when turning of the rotary knob is
detected. During the switch position delay, the values at the outputs are not changed. When
the switch position delay has expired, the temporary key position is accepted as the current
key position. The status of the outputs is changed in accordance with this position.
Settings
Description
Default setting
0
Switch position delay: disabled
1 Switch position delay: Minimum value 20 (2 seconds)
100
Switch position delay: Maximum value
Increment: 0.1 seconds
10.2.3.7
"Select memory range" parameter
"Select memory range" parameter
The Port Configuration Tool
S7-PCT
includes a dropdown menu with which you can select
the part of the data set to be displayed. The memory range in which the individually
encodable ID keys are saved can be selected and displayed.
Settings
Description
Default setting
1 Select memory range: Minimum value 1 (individually encodable key
1 ... 10)
5
Select memory range: Maximum value
Increment: 10 keys