User Manual

IO-Link
10.2 Design of a command point with ID key-operated switch
SIRIUS ACT 3SU1 pushbuttons and signaling devices
System Manual, 02/2015, A5E03457306020A/RS-AB/002
223
"Delete individual ID key" parameter
To delete an individually encodable ID key from the key list, the following steps are required.
Procedure:
Use individually encodable ID key in the ID key-operated switches
Wait for detection of the ID key
Write the system command "Delete individual ID key" (value 0xA5 in data set (index) 2 -
system commands or button in the Port Configuration Tool
S7-PCT
)
Check: Status of the individually encodable ID key (data set (index) 92 - diagnostics)
Remove the ID key from the ID key-operated switch
Settings
Description
165
Delete individual ID key used in the ID key-operated switch.
Status of the individually encodable ID key (data set (index) 92 - diagnostics, byte
19.0 ... 19.7)
You will find additional information in Chapter "Data set (Index) 92 - diagnostics (Page 282)".
Value
Description
0 Individually encodable ID key detected.
2
No valid individually encodable ID key used.
3
Deleted ID key not in the memory of the electronic module.
Delete individually encodable ID key using data set 80
If the individually encodable ID key is lost or stolen, it is possible to remove the individually
encodable ID key from the key list without the individually encodable ID key being physically
available.
In this case, the electronics module offers the option of deleting the key from the key list
using data set 80.
Procedure:
To delete an individually encodable key from the list using data set 80, the following steps
are required:
Write the identification number of the ID key to be deleted to data set (index) 80, or enter
it in a form field in the Port Configuration Tool
S7-PCT
Load the entered identification number into the electronic module in the
Port Configuration Tool
S7-PCT
Write the system command "Delete individually encodable ID key using data set 80"
(value 0xA6 in data set (index) 2 - system commands or button in the
Port Configuration Tool
S7-PCT
)
Check: Status of the individually encodable ID key (data set (index) 92 - diagnostics)