Data Sheet

● for short-circuit protection of the auxiliary switch
required
gG: 16 A (500 V, 1 kA)
Installation/ mounting/ dimensions
Mounting position +/-22,5° rotation possible on vertical mounting surface; can be
tilted forward and backward by +/- 22.5° on vertical mounting
surface; standing, on horizontal mounting surface
Mounting type screw fixing
● Side-by-side mounting
Yes
Height 240mm
Width 180mm
Depth 236mm
Required spacing
● with side-by-side mounting
— forwards
20mm
— Backwards
0mm
— upwards
10mm
— downwards
10mm
— at the side
10mm
● for grounded parts
— forwards
70mm
— Backwards
0mm
— upwards
10mm
— at the side
10mm
— downwards
10mm
● for live parts
— forwards
70mm
— Backwards
0mm
— upwards
10mm
— downwards
10mm
— at the side
10mm
Connections/ Terminals
Type of electrical connection screw-type terminals
● for main current circuit
screw-type terminals
● for auxiliary and control current circuit
screw-type terminals
Type of connectable conductor cross-sections
● for auxiliary contacts
— single or multi-stranded
2x (1 ... 2,5 mm²)
— finely stranded with core end processing
2x (0,75 ... 2,5 mm²)
Safety related data
Protection against electrical shock finger-safe only with terminal cover
Certificates/ approvals
3TC5217-0LB4 Subject to change without notice
Page 4/
7
09/14/2019 © Copyright Siemens