Data Sheet

● input for analog temperature sensors
Yes
● input for ground fault detection
Yes
● Relay output
Yes
Insulation voltage
● with degree of pollution 3 rated value
300V
Surge voltage resistance rated value 4000V
Protection class IP IP20
Shock resistance
● when mounted on current measuring module
acc. to IEC 60068-2-27
10 g / 11 ms
● acc. to IEC 60068-2-27
15g / 11 ms
Vibration resistance
● acc. to IEC 60068-2-6
1 ... 6 Hz: 15 mm, 6 ... 500 Hz: 2g
● when mounted on current measuring module
acc. to IEC 60068-2-6
1 ... 4 Hz / 15 mm, 4 ... 500 Hz / 1g
Switching capacity current of the NO contacts of the
relay outputs at AC-15
● at 24 V
6A
● at 120 V
6A
● at 230 V
3A
Switching capacity current of the NO contacts of the
relay outputs at DC-13
● at 24 V
2A
● at 60 V
0.55A
● at 125 V
0.25A
Mechanical service life (switching cycles)
● typical
10000000
Electrical endurance (switching cycles)
● typical
100000
Buffering time in the event of power failure 0.02s
Reference code acc. to DIN EN 81346-2 F
Reference code acc. to DIN EN 61346-2 B
Continuous current of the NO contacts of the relay
outputs
● at 50 °C
6A
● at 60 °C
5A
Certificate of suitability
● according to ATEX directive 2014/34/EU
BVS 06 ATEX F001
Explosion device group and category according to
ATEX directive 2014/34/EU
II (2) G, II (2 ) D, I (M2)
Measurable temperature
● with NTC minimum
80°C
● with NTC maximum
160°C
3UF7600-1AB01-0 Subject to change without notice
Page 2/
10
09/13/2019 © Copyright Siemens