Data Sheet

● during operation acc. to IEC 60721
3K6 (no formation of ice, no condensation, relative humidity 10 ...
95%), 3C3 (no salt mist), 3S2 (sand must not get into the
devices), 3M6
● during storage acc. to IEC 60721
1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt
mist), 1S2 (sand must not get into the devices), 1M4
● during transport acc. to IEC 60721
2K2, 2C1, 2S1, 2M2
Relative humidity
● during operation
10...95%
Contact rating of auxiliary contacts according to UL B300 / R300
Short-circuit protection
Design of short-circuit protection
● per output
Fuse links: gG 6 A, quick-response 10 A (IEC 60947-5-1),
miniature circuit-breaker C char.: 1.6 A (IEC 60947-5-1) or 6 A
(I_K < 500 A)
Safety related data
Protection against electrical shock finger-safe
Galvanic isolation
(electrically) protective separation acc. to IEC 60947-
1
All circuits with protective separation (double creepage paths and
clearances), the information in the "Protective Separation" test
report, No.A0258, must be observed (link see further information)
Galvanic isolation
● between inputs and electronic
No
Control circuit/ Control
Operating range factor control supply voltage rated
value at DC
● initial value
0.8
● Full-scale value
1.2