User Manual

3UG4625 residual current monitoring relay with 3UL23 transformer
9.7 Technical data
3UG4 / 3RR2 monitoring relays
Manual, 02/2013, NEB927043002000/RS-AA/002
201
9.7 Technical data
Measuring circuit
3UG4625-.....
Type of current for monitoring AC
16 Measurable line frequency Hz
400
Adjustable response current
1
A
0.03 … 40
2
A 0.03 … 40
Adjustable response delay time when starting s
0.1 … 20
Adjustable response delay time s 0.1 … 20
Switching hysteresis % 0 … 50
Stored energy time at mains power cut minimum ms 10
Operating voltage
rated value
V
24 … 240
General technical details
3UG4625-.....
Product function for three-phase supplies
Design of the display LCD
Product function
difference current indication
Yes
defect storage
Yes
overcurrent recognition of 1 phase
Yes
undercurrent recognition of 1 phase
No
reset external
Yes
open-circuit or closed-circuit current principle
Yes
Starting time after the control supply voltage has been applied ms
1 600
Response time maximum ms 150
Relative metering precision % 5
Precision of digital display +/-1 digit
Temperature drift per °C %/°C 0.1
Relative repeat accuracy % 1