Industrial Controls Monitoring and Control Devices 3UG4 / 3RR2 Monitoring Relays Manual Edition 02/2013
3UG4 / 3RR2 monitoring relays Industrial Controls Monitoring and control devices 3UG4 / 3RR2 monitoring relays Manual 1 ___________________ Introduction 2 ___________________ Safety information 3 ___________________ System overview 3RR2 current monitoring 4 ___________________ relays 3UG4501 filling level 5 ___________________ monitoring relay 6 ___________________ 3UG4.
Legal information Warning notice system This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger.
Table of contents 1 Introduction.............................................................................................................................................. 11 2 Safety information.................................................................................................................................... 13 3 4 2.1 Standards.....................................................................................................................................13 2.
Table of contents 4.5.3 4.5.4 4.5.5 4.5.6 5 6 Operation..................................................................................................................................... 62 Diagnostics.................................................................................................................................. 65 Circuit diagrams .......................................................................................................................... 66 Technical data...............
Table of contents 7 8 6.5.6 Technical data............................................................................................................................125 6.6 6.6.1 6.6.2 6.6.3 6.6.4 6.6.4.1 6.6.4.2 6.6.5 6.6.6 3UG4615 / 3UG4616 line monitoring relays ..............................................................................129 Operator controls and connection terminals ..............................................................................129 Functions.......................
Table of contents 8.7 9 10 11 Technical data........................................................................................................................... 183 3UG4625 residual current monitoring relay with 3UL23 transformer...................................................... 187 9.1 Application areas....................................................................................................................... 187 9.2 Operator controls and connection terminals .................
Table of contents 12 13 14 11.2.2 Functions....................................................................................................................................261 11.3 11.3.1 11.3.2 3UG4633 voltage monitoring relay ............................................................................................263 Operator controls and connection terminals ..............................................................................263 Functions............................................
Table of contents 14.2 14.2.1 14.2.2 14.2.3 14.2.4 14.2.5 14.2.5.1 14.2.5.2 14.2.5.3 14.2.5.4 14.2.5.5 14.2.5.6 14.2.5.7 14.2.5.8 Accessories for 3UG4 monitoring relays................................................................................... 315 Sealable cover .......................................................................................................................... 315 Push-in lugs ...................................................................................................
Introduction 1 Purpose of the manual This manual describes the 3UG4 monitoring relays for stand-alone assembly and the 3RR2 current monitoring relays for mounting on 3RT2 contactors The manual provides overview information for integrating the monitoring relays into the system environment, and it describes the hardware and software components of the devices. The information in this manual enables you to commission the monitoring relays.
Introduction Up-to-the-minute information You can obtain further assistance by calling the following numbers: Technical Assistance: Telephone: +49 (0) 911-895-5900 (8 a.m. to 5 p.m. CET) Fax: +49 (0) 911-895-5907 or on the Internet at: E-mail: (mailto:technical-assistance@siemens.com) Internet: (www.siemens.com/industrial-controls/technical-assistance) Correction sheet A correction sheet is included at the end of the manual.
2 Safety information 2.
Safety information 2.2 Product-specific safety information 2.2 Product-specific safety information Intended use WARNING Intended use Can Cause Death, Serious Injury, or Property Damage. The devices may only be used for the applications described in the catalog and the technical description, and only in conjunction with equipment or components from other manufacturers which have been approved or recommended by Siemens.
Safety information 2.3 Approvals, test certificates, characteristics 2.3 Approvals, test certificates, characteristics Approvals, test certificates, characteristics You can find an overview of the certifications available for low-voltage controls and distribution products and other technical documentation, updated daily, on the Internet (www.siemens.com/industrial-controls/support). You will find further information in the Catalog IC 10 - SIRIUS "Industrial Controls," Chapter 10 (www.siemens.
Safety information 2.
System overview 3.1 3 Product description Product description The tried and tested SIRIUS monitoring relays for electrical and mechanical quantities enable constant monitoring of all important characteristic quantities that provide information about the reliability performance of the plant. Sudden disturbances and gradual changes, which may reveal a maintenance requirement, for example, are both indicated.
System overview 3.2 Application planning 3.2 Application planning The following information must be taken into account when planning applications involving the SIRIUS monitoring relays. Installation altitude The monitoring relays are approved for installation altitudes up to 2,000 m. The reduced air density at altitudes higher than 2,000 meters affects the electrical characteristics of the monitoring relays.
System overview 3.3 Connection methods 3.3 Connection methods 3.3.1 Screw-type connection Screw-type connection Use the following tool to establish the connection: All SIRIUS monitoring relays feature size PZ 2 screws for Pozidriv screwdrivers. The devices have screw terminals with captive screws and washers. The screw terminals also allow for the connection of 2 conductors with different cross-sections.
System overview 3.3 Connection methods Connection cross-sections of the permanently connected terminal blocks with screw-type connections The following table lists the permissible conductor cross-section for the main conductor terminals of the 3RR2 current monitoring relays with analog and digital setting (size S00 and S0) with screw-type connection.
System overview 3.3 Connection methods 3.3.2 Spring-loaded connection Spring-loaded connection Without exception, all SIRIUS monitoring relays have spring-loaded connections. They make wiring quick and maintenance-free, while also meeting high demands in terms of vibration and shock resistance.
System overview 3.3 Connection methods Catalog IC10 "Industrial Controls" (www.siemens.com/industrial-controls/catalogs) offers a standard screwdriver (3 mm slot) that can be used as the operating tool for opening the spring-loaded connections. Spring-loaded connection for mountable 3RR2 current monitoring relays The table below describes the procedure for creating a spring-loaded connection: DANGER Hazardous Voltage. Will cause death or serious injury.
System overview 3.3 Connection methods Note Damage to spring-loaded terminal on the 3RR2 current monitoring relay! If you insert the screwdriver into the central opening on the spring-loaded terminal, this could damage the terminal. Do not insert the screwdriver into the central opening on the spring-loaded terminal.
System overview 3.3 Connection methods Connection cross-sections of the removable terminal blocks with spring-loaded connections Table 3- 5 Removable terminal block with spring-loaded connections - monitoring relays Removable terminal Tool Ø3.0 x 0.5 (3RA2908-1A) Solid and stranded 2 x (0.25 to 1.5) mm² Finely stranded without end sleeve 2 x (0.25 to 1.5) mm² Finely stranded with end sleeve 2 x (0.25 to 1.
System overview 3.3 Connection methods 3.3.3 Device replacement by means of removable terminals DANGER Hazardous Voltage Will cause death or serious injury. Turn off and lock out power before working on this equipment. The removable terminals of the monitoring relays facilitate device replacement when necessary. The mechanical coding on the terminals prevents mix-ups. Note The terminals can only be dismantled in the following order due to their arrangement on the monitoring relay: 1.
System overview 3.4 Mounting / removal 3.4 Mounting / removal 3.4.1 Mounting 3RR2 current monitoring relay Mounting options 3RR2 current monitoring relays are matched to 3RT2 contactors and 3RF34 (size S0) solidstate contactors in terms of their electrical and mechanical features. As a result, direct mounting can be achieved easily. Alternatively, the devices can also be installed individually in the case of stand-alone assembly or if a 3RU2 / 3RB3 overload relay is being used at the same time.
System overview 3.4 Mounting / removal Direct mounting on 3RT2 contactor / 3RF34 (size S0) solid-state contactor The diagram below shows an example mounting scenario based on mounting the 3RR21 analog setting current monitoring relay, size S0, on the 3RT2 contactor. Table 3- 7 Mounting of 3RR2 current monitoring relay, screw-type connection system (size S0) Step Operating instruction 1 Push the current monitoring relay into the contactor from below.
System overview 3.4 Mounting / removal Table 3- 8 Mounting of 3RR2 current monitoring relay, spring-loaded connection system (size S0) Step Operating instruction 1 Insert the contacts (a) into the central opening of the spring-loaded terminals on the contactor (see below, a), with the contacts flush to the right. Make sure that the guide tabs (zoom view) are inserted into the designated slots on the contactor.
System overview 3.4 Mounting / removal Disassembly To disassemble the S00 / S0 assemblies from the DIN rail, press the contactor down and pull it toward you. Table 3- 9 Removing the 3RR2 current monitoring relay, screw-type connection system (size S0) Step Operating instruction 1 Undo the screws on the main conductor terminals. 2 Pull the current monitoring relay down and away from the contactor.
System overview 3.4 Mounting / removal Separately mounted Note The accessories required for separate mounting are described in Chapter "Terminal support for stand-alone assembly (Page 312)." 3.4.2 Mounting the 3UG4 monitoring relay Mounting position It can be mounted in any position. Screw mounting The illustration below shows how to screw-mount the 3UG4 monitoring relay.
System overview 3.4 Mounting / removal Standard-rail mounting The illustration below shows how to mount the 3UG4 monitoring relay onto a standard rail. Table 3- 12 Mounting the monitoring relay (mounting on and removing from standard rail) Step Operating instruction 1 Position the device on the top edge of the mounting rail and press it down until it snaps onto the bottom edge of the rail.
System overview 3.4 Mounting / removal 3.4.3 Installing the 3UG458. monitoring relay. Rail mounting The figure below shows how to install the 3UG458. insulation monitoring relay on a standard rail. Table 3- 13 Installing the 3UG458. insulation monitoring relay (mounting onto standard rail) Step Instructions 1/2 Position the device on the top edge of the DIN rail and press down until it snaps onto the bottom edge of the DIN rail. Table 3- 14 Figure Removing the 3UG458.
System overview 3.5 Overview of the functions 3.5 Overview of the functions 3.5.
System overview 3.5 Overview of the functions 3.5.
System overview 3.
System overview 3.6 Menu-based operation 3.6 Menu-based operation Operator controls The digitally adjustable monitoring relays have three keys for navigating on the menu levels: ● SET key for navigating to the menu levels and for switching between the menu levels ● 2 arrow keys for setting parameters Navigation through the menu system of the monitoring relays is explained below in a schematic diagram.
System overview 3.6 Menu-based operation Menu-based operation 581 9$/8( 2. Threshold1 0HDV9DOXH Threshold2 0HDV9DOXH (5525 12 (5525 0HPRU\ \HV ! V 12 (5525 0HPRU\ QR Threshold3 (5525 (UURU (UURU ... (UURU 6(7 Parameter1 Parameter2 ! V ① ② ③ ... V RUN - OK • Parameter3 Status display in the correct range, see below Measured value1 / Measured value2 / ...
System overview 3.6 Menu-based operation Menu levels "RUN" and "SET" 1 3 2 The RUN menu shows the up-to-date current measured value ①. You can use the arrow keys to change between the individual measuring values on devices with multiple outputs. In this case, the display automatically switches between the name of the measured value and the actual measured value. ② represents the selected type of monitoring (overshoot, undershoot, or range monitoring).
System overview 3.6 Menu-based operation Navigation in the menu There are basically two ways of navigating on both menu levels: ● Brief pressing the SET key (≤ 0.5 s) You can jump from one parameter to the next within one menu level by briefly pressing the SET key Entry . The order is not variable. Display at the RUN menu level Display at the SET menu level 1. Current measuring value (MeasValue1 / MeasValue2 / ...) or error symbol (Error1 / Error2 / Error3 / ...
System overview 3.6 Menu-based operation Note Aborting the menu switchover The switchover process will be interrupted if the SET key is released while or displayed. The menu will revert to the menu command you were working with when the switch was initiated. is Note Reset in the event of an error To reset the device, it is necessary to press both arrow keys simultaneously for more than 2.5 s after removal of the cause of error and with Hand-RESET active. While the keys are appears on the display.
3RR2 current monitoring relays 4.1 4 Product description Overview SIRIUS 3RR2 current monitoring relays are suitable for current monitoring of motors or other loads. They are capable of two-phase or three-phase monitoring of the rms value of AC currents, checking that the values do not overshoot or undershoot set thresholds.
3RR2 current monitoring relays 4.2 Application areas 4.
3RR2 current monitoring relays 4.3 Performance features of current monitoring relays 4.3 Table 4- 2 Performance features of current monitoring relays Performance features of 3RR2 current monitoring relays Functions/Parameters Current monitoring relays with analog setting Current monitoring relays with digital setting 3RR2141-.A.30 3RR2142-.A.30 3RR2241-.F.30 3RR2242-.F.30 Rated current 1.6 to 16 A 4 to 40 A 1.
3RR2 current monitoring relays 4.3 Performance features of current monitoring relays 4.3.
3RR2 current monitoring relays 4.3 Performance features of current monitoring relays 4.3.
3RR2 current monitoring relays 4.4 3RR21 current monitoring relays 4.4 3RR21 current monitoring relays 4.4.
3RR2 current monitoring relays 4.4 3RR21 current monitoring relays 4.4.2 Function General functionality Depending on the setting, the current monitoring relays monitor an AC load current that flows through terminals 1L1 / 2T1 and 3L2 / 4T2 of the device for overshoot (I▲) or undershoot (I▼) or in range monitoring (I▲ and I▼ ≠ OFF). Depending on their design, the current monitoring relays are powered with a 24 V AC/DC or 24 to 240 V AC/DC supply voltage through terminals B1/B2.
3RR2 current monitoring relays 4.4 3RR21 current monitoring relays Function diagrams Memory = O: 2 I▲ Memory = I: 2 I % % I % % I▼ = Off a, !, , , + \VW 1. 2 2 !, I I 2. + \VW , a, a, )$8/7 /(' OFF F LASH slow O F F F LASH O F F slow F LASH slow onD el onD el I D el ON OFF F LASH fast OFF )$8/7 /(' OFF F LASH slow OFF F LASH slow % % OFF I D el % % I▼ , 1. 2 2 , a, + \VW 2.
3RR2 current monitoring relays 4.4 3RR21 current monitoring relays 4.4.
3RR2 current monitoring relays 4.4 3RR21 current monitoring relays Required tools The same screwdriver can be used to set the parameters as for mounting the current monitoring relays. 4.4.
3RR2 current monitoring relays 4.4 3RR21 current monitoring relays 4.4.6 Technical data General technical specifications 3RR2141-..... 3RR2142-.....
3RR2 current monitoring relays 4.4 3RR21 current monitoring relays 3RR2141-..... Standby time for restart after fault s 3RR2142-..... 0.
3RR2 current monitoring relays 4.4 3RR21 current monitoring relays Connections 3RR2141 (size S00) 3RR2141-1.... 3RR2141-2....
3RR2 current monitoring relays 4.4 3RR21 current monitoring relays Connections 3RR2142 (size S0) 3RR2142-1.... 3RR2142-2....
3RR2 current monitoring relays 4.4 3RR21 current monitoring relays Mounting, fixing, dimensions 3RR2141-1.... Built in orientation any Type of mounting direct mounting 3RR2142-1.... 3RR2141-2.... 3RR2142-2....
3RR2 current monitoring relays 4.4 3RR21 current monitoring relays Auxiliary circuit 3RR2141-..... Design of the contact element of the output relay Operating current at 17 V minimum 3RR2142-.....
3RR2 current monitoring relays 4.4 3RR21 current monitoring relays Supply voltage 3RR214.-..A.. Type of voltage of supply voltage 3RR214.-..W..
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays 4.5 3RR22 current monitoring relays 4.5.
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays You will find additional information on the connection terminals and the permissible conductor cross-sections in Chapter "Connection methods (Page 19)." You will find information on connecting in Chapter "Circuit diagrams (Page 66)." 4.5.
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays Reset response If the device is set to automatic reset, the CO contact and the semiconductor output will respond once a previously occurring error has been dealt with and the reclosing delay time has elapsed. A previously occurring error is, therefore, not saved. If manual RESET is selected, the CO contact remains in the current switching state even if a previously occurring error has been dealt with.
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays Function diagrams Display Memory = no Memory = no Relay switching behavior = NC (closed-circuit principle) Relay switching behavior = NO (open-circuit principle) I▲ / I!▲ % % % % I▼ / I!▼ = Off !, !Q [ , !, n x I▲ Q [ ,Ⴃ Q [ ,Ⴃ ,Ⴃ , Ⴃ ,Ⴃ , Ⴃ + \VW a , a , 4 RQ 4 RII 4 RQ 4 RII + \VW onD el onD el I▲ / I!▲ = Off I >> onD el D el R sD el D el R sD el R sD e
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays Display I▲ / I!▲ = Off Memory = no Memory = no Relay switching behavior = NC (closed-circuit principle) Relay switching behavior = NO (open-circuit principle) % % % % I▼ / I!▼ !, , , , a , , + \VW + \VW , , a + \VW + \VW , , 4 RQ 4 RII 4 RQ 4 RII onD el % % / / / onD el D el R sD el D el onD el R sD el onD el D el R sD el D el
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays Parameter information The table below shows the settable parameter information of the 3RR22 current monitoring relay with digital setting: Table 4- 7 Menu level Parmeter information, 3RR22 current monitoring relays with digital setting Parameters Setting range Minimum value OFF1) Increment Factory setting Maximum value "RUN" Threshold for current undershoot(I▼) 1.6 A or 4 A or OFF2) 16 A or OFF1) 40 A or OFF2) 0.1 A 1.
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays Note The "current overshoot" or "current undershoot" monitoring mode is defined with the setting OFF for the upper and lower threshold.
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays 4.5.4 Diagnostics Display information The display is divided into three different areas. 1 3 2 ① ② ③ Current measured value or fault symbol Type of monitoring Symbols for the semiconductor contact (left) and the CO contact (right) Meaning of the information on the display Note Indications in the event of a fault The symbols on the display flash to indicate an error.
3RR2 current monitoring relays 4.
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays 4.5.6 Technical data General technical specifications 3RR2241-..... 3RR2242-.....
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays 3RR2241-..... Standby time for restart after fault s 3RR2242-..... 0.
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays 3RR2241-..... Temperature drift per °C %/°C 0.1 3RR2242-..... Current-carrying capacity • for permanent overcurrent maximum permissible A 16 40 • for overcurrent duration < 1 s maximum permissible A 320 800 3RR2241-1.... 3RR2241-2....
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays 3RR2241-1.... 3RR2241-2.... Tightening torque • with screw-type terminals N·m 0.8 … 1.2 CE / UL / CSA Verification of suitability Connections 3RR2242 (size S0) 3RR2242-1.... 3RR2242-2....
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays Mounting, fixing, dimensions 3RR2241-1.... Built in orientation any Type of mounting direct mounting 3RR2242-1.... 3RR2 241-2.... 3RR2 242-2....
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays Auxiliary circuit 3RR2241-..... Design of the contact element of the output relay Operating current at 17 V minimum 3RR2242-..... closed-circuit current / open-circuit current mA Number of outputs as contact-less semiconductor switching element for reporting function nondelayed 5 1 Current-carrying capacity of the semiconductor output • at DC-13 at 240 V mA 20 • at AC-14 at 240 V at 50/60 Hz mA 20 mA 0.
3RR2 current monitoring relays 4.5 3RR22 current monitoring relays Supply voltage 3RR224.-..A.. Type of voltage of supply voltage 3RR224.-..W..
3RR2 current monitoring relays 4.
3UG4501 filling level monitoring relay 5.1 5 Application areas Application areas The 3UG4501 filling level monitoring relays are used, for example, in the following applications: Table 5- 1 Application areas of the 3UG4501 filling level monitoring relay Function • One-point filling level monitoring and twopoint filling level monitoring • Overflow protection • Dry-run protection • Leakage monitoring Application • Open-loop control of a bilge pump, e.g.
3UG4501 filling level monitoring relay 5.2 Operator controls and connection terminals 5.2 Operator controls and connection terminals Front view / terminal labeling Front view Description M A1+ 24V SIRIUS UN 30 10 100 2 200kΩ R sens Delay 5 3 0,5 7 10s 3UG4501-..... Position digits ① Terminal block (removable): Connection is possible using screw terminals or spring-loaded terminals. ② Rotary button for setting the monitoring mode.
3UG4501 filling level monitoring relay 5.3 Functions 5.3 Functions General functionality The 3UG4501 filling level monitoring relays and the connectable 2-pole or 3-pole 3UG3207-.. probes are used to monitor the filling levels of electrically conductive liquids.
3UG4501 filling level monitoring relay 5.3 Functions Probes for filling level monitoring To monitor filling levels of electrically conductive liquids, the following probes can be mounted on the 3UG4501 filling level relays. ● Three-pole wire electrode ● Two-pole wire electrode ● Two-pole bow electrode ● Single-pole bow electrode for side mounting ● Single-pole rod electrode for side mounting These necessary accessories are described in Chapter "Probes for the 3UG4501 monitoring relay (Page 317).
3UG4501 filling level monitoring relay 5.3 Functions Function diagrams 3UG4501 Drainage control (OV 1)), two-point closed-loop control Inflow control (UN 2)), two-point closed-loop control Reset Reset A1/A2 A1/A2 > 0,5 s + t Max Min > 0,5 s + t Max t t t Min t 11/14 11/14 11/12 11/12 t t t = Delay 0.5 - 10 s 1) OV= overshoot 2) UN= undershoot t t t = Delay 0.
3UG4501 filling level monitoring relay 5.4 Operation 5.4 Operation Parameters The following parameters can be set on the relevant rotary button using a screwdriver: Table 5- 2 Parameter information, 3UG4501 filling level monitoring relay Parameters Operating elements 2) Setting range Minimum value Maximum value Monitoring mode1): drainage control (OV) or inflow control (UN) 3 -- -- -- Sensor sensitivity (R sens) 4 2 kΩ 200 kΩ Continuous Tripping delay time (Delay) 5 0.
3UG4501 filling level monitoring relay 5.6 Circuit diagrams 5.6 Circuit diagrams Internal circuit diagram 3UG4501-.A.30 $ 0D[ 0LQ 0 3UG4501 $ ದ Figure 5-1 3UG4501-.A.30 filling level monitoring relay Wiring examples Drainage control AC/+U AC/+U K1 A1 (+) Max Min 11 12 14 M K1 A1 (+) Max Min 11 12 14 M 3UG45 01 3UG45 01 K1 K1 29 29 5 VHQV 'HOD\ 5 VHQV 'HOD\ A2 (–) A2 (–) AC/0V AC/0V Two-step control One-point closed-loop control 3UG4 / 3RR2 monitoring rela
3UG4501 filling level monitoring relay 5.6 Circuit diagrams Inflow control AC/+U A1 (+) AC/+U Max Min 3UG45 01 11 K1 12 14 M K1 A1 (+) Max Min 3UG45 01 M K1 81 81 5 VHQV 'HOD\ 5 VHQV 'HOD\ A2 (–) A2 (–) AC/0V AC/0V Two-step control 11 K1 12 14 One-point closed-loop control 3UG4 / 3RR2 monitoring relays 82 Manual, 02/2013, NEB927043002000/RS-AA/002
3UG4501 filling level monitoring relay 5.7 Technical data 5.7 Technical data General technical details 3UG4501-..A.. Product function Response time maximum s 0.3 Relative metering precision % 20 Temperature drift per °C %/°C 1 Relative repeat accuracy % 1 Manufacturer article number of the optional sensor Cable length of the sensor maximum 3UG4501-..W..
3UG4501 filling level monitoring relay 5.7 Technical data 3UG4501-..A.. Continuous current of the DIAZED fuse link of the output relay A 3UG4501-..W.. 4 Resistance against vibration according to IEC 60068-2-6 1 ... 6 Hz: 15 mm, 6 ...
3UG4501 filling level monitoring relay 5.7 Technical data 3UG4501-..A.. Mechanical operating cycles as operating time typical 10 000 000 Electrical operating cycles as operating time at AC-15 at 230 V typical 100 000 Operating cycles with 3RT2 contactor maximum 1/h 3UG4501-..W.. 5 000 Mechanical design 3UG4501-1.... Width mm 22.5 Height mm 92 Depth mm 91 Built in orientation 3UG4501-2....
3UG4501 filling level monitoring relay 5.7 Technical data Design of the electrical connection 3UG4501-1.... 3UG4501-2.... screw-type terminals spring-loaded terminals 1x (0.5 ... 4 mm2), 2x (0.5 ... 2.5 mm2) 2x (0.25 ... 1.5 mm2) Type of the connectable conductor cross-section • solid • finely stranded • – with wire end processing 1x (0.5 ... 2.5 mm2), 2x (0.5 ... 1.5 mm2) 2 x (0.25 ... 1.5 mm2) – without wire end processing — 2x (0.25 ... 1.5 mm2) for AWG conductors – solid 2x (20 ..
3UG4.1 line monitoring relay 6 Overview The electronic line monitoring relays permit maximum protection for mobile machines and plants or in unstable power systems. Using the monitoring relays, line and voltage errors can be detected early and minimized.
3UG4.1 line monitoring relay 6.1 Application areas 6.1 Application areas Application areas The various line monitoring relays are used, for example, in non-stationary systems such as refrigeration containers, construction site compressors, and cranes.
3UG4.1 line monitoring relay 6.2 3UG4511 line monitoring relay 6.2 3UG4511 line monitoring relay 6.2.1 Operator controls and connection terminals Front view / terminal labeling 3UG4511 Front view Description L2 L1 SIRIUS L3 3 160-260V Position digits ① Terminal block (removable) Connection is possible using screw-type terminals or spring-loaded terminals.
3UG4.1 line monitoring relay 6.2 3UG4511 line monitoring relay 6.2.2 Function General functionality The 3UG4511 line monitoring relays monitor the phase sequence in a three-phase system. The devices are self-powered (measuring voltage = rated control supply voltage) and work on the closed-circuit principle. Depending on the version, the line monitoring relays are powered with a rated control supply voltage of 160 V to 260 V (3UG4511-..N20), 320 to 500 V (3UG4511-..P20) and 420 to 690 V (3UG4511-..
3UG4.1 line monitoring relay 6.2 3UG4511 line monitoring relay Function diagrams 3UG4511 Correct phase sequence Incorrect phase sequence L1-L2-L3 L3-L2-L1 11/14 11/14 11/12 OFF 11/12 21/24 21/24 21/22 21/22 ON 6.2.3 Diagnostics 6.2.3.
3UG4.1 line monitoring relay 6.2 3UG4511 line monitoring relay 6.2.4 Circuit diagrams Internal circuit diagrams 3UG4511 3UG4511-.A.. / 3UG4511-.B.. / / / 8* / / 8* 3UG4511-.A.. line monitoring relay 3UG4511-.B.. line monitoring relay Note It is not necessary to fuse the measuring circuit to protect the device. Fusing for line protection depends on the cross-section used.
3UG4.1 line monitoring relay 6.2 3UG4511 line monitoring relay 6.2.5 Technical data Measuring circuit 3UG4511-..N 3UG4511-..P 3UG4511-..Q 160 … 260 320 … 500 420 … 690 3UG45 11-..N 3UG45 11-..P 3UG45 11-..
3UG4.1 line monitoring relay 6.2 3UG4511 line monitoring relay 3UG45 11-..N Type of voltage of the controlled supply voltage 3UG45 11-..P 3UG45 11-..
3UG4.1 line monitoring relay 6.2 3UG4511 line monitoring relay 3UG45 11-..N Electrostatic discharge according to IEC 61000-4-2 6 kV contact discharge / 8 kV air discharge Field-bound parasitic coupling according to IEC 61000-4-3 10 V/m Thermal current of the contactA affected switching element maximum 5 Insulation voltage for overvoltage category III according to IEC 60664 with degree of pollution 3 rated value 690 V Degree of pollution 3UG45 11-..P 3UG45 11-..
3UG4.1 line monitoring relay 6.2 3UG4511 line monitoring relay Mechanical design 3UG4511-1A... Width mm 22.5 Height mm 83 Depth mm 91 Built in orientation 3UG4511-1B... 3UG4511-2A... 3UG4511-2B...
3UG4.1 line monitoring relay 6.2 3UG4511 line monitoring relay 3UG4511-1A... Design of the electrical connection 3UG4511-1B... 3UG4511-2A... 3UG4511-2B... screw-type terminals spring-loaded terminals 1x (0.5 ... 4 mm2), 2x (0.5 ... 2.5 mm2) 2x (0.25 ... 1.5 mm2) Type of the connectable conductor cross-section • solid • finely stranded • – with wire end processing 1x (0.5 ... 2.5 mm2), 2x (0.5 ... 1.5 mm2) 2 x (0.25 ... 1.5 mm2) – without wire end processing — 2x (0.25 ... 1.
3UG4.1 line monitoring relay 6.3 3UG4512 line monitoring relay 6.3 3UG4512 line monitoring relay 6.3.1 Operator controls and connection terminals Front view / terminal labeling 3UG4512 Front view Description L2 L1 SIRIUS L3 3 160-690V Phase loss Phase sequence L1 L2 L3 11 21 L 12 14 22 24 3UG4512-..... 12 22 11 21 14 24 Position digits ① Terminal block (removable) Connection is possible using screw-type terminals or spring-loaded terminals.
3UG4.1 line monitoring relay 6.3 3UG4512 line monitoring relay 6.3.2 Function General functionality The 3UG4512 line monitoring relays monitor the phase sequence and the phase failure of one of the three phases in a three-phase system. The asymmetry threshold is 10 %. The devices are self-powered (measuring voltage = rated control supply voltage) and work on the closed-circuit principle.
3UG4.1 line monitoring relay 6.
3UG4.1 line monitoring relay 6.3 3UG4512 line monitoring relay 6.3.3 Diagnostics 6.3.3.
3UG4.1 line monitoring relay 6.3 3UG4512 line monitoring relay 6.3.4 Circuit diagrams Internal circuit diagrams 3UG4512 3UG4512-.A.. / 3UG4512-.B.. / / / 8* / / 8* 3UG4512-.A.. line monitoring relay 3UG4512-.B.. line monitoring relay Note It is not necessary to fuse the measuring circuit to protect the device. Fusing for line protection depends on the cross-section used.
3UG4.1 line monitoring relay 6.3 3UG4512 line monitoring relay 6.3.5 Technical data Measuring circuit 3UG4512-..... Type of voltage for monitoring AC Number of poles for main current circuit 3 Measurable voltage • for AC Adjustable voltage range V 160 … 690 V —… General technical details 3UG4512-.....
3UG4.1 line monitoring relay 6.3 3UG4512 line monitoring relay 3UG4512-.....
3UG4.1 line monitoring relay 6.3 3UG4512 line monitoring relay 3UG4512-.....
3UG4.1 line monitoring relay 6.3 3UG4512 line monitoring relay 3UG4512-1A... 3UG4512-1B... 3UG4512-2A... 3UG4512-2B... Distance, to be maintained, conductive elements • forwards mm 0 • backwards mm 0 • sidewards mm 0 • upwards mm 0 • downwards mm 0 Type of mounting snap-on mounting Product function removable terminal for auxiliary and control circuit Yes Design of the electrical connection screw-type terminals spring-loaded terminals 1x (0.5 ... 4 mm2), 2x (0.5 ... 2.
3UG4.1 line monitoring relay 6.4 3UG4513 line monitoring relay 6.4 3UG4513 line monitoring relay 6.4.1 Operator controls and connection terminals Front view / terminal labeling 3UG4513 Front view Description L2 L1 SIRIUS L3 3 160-690V 3 Un 400 500 600 300 200 Phase loss Phase sequence 690V Delay 8 L1 L2 L3 L < Un 12 16 4 20 s 0,1 Position digits ① Terminal block (removable) Connection is possible using screw-type terminals or spring-loaded terminals.
3UG4.1 line monitoring relay 6.4 3UG4513 line monitoring relay 6.4.2 Function General functionality The 3UG4513 line monitoring relays monitor for phase sequence, phase failure of one of the three phases, and undershoot of at least one line-to-line voltage of the set nominal line voltage by 20 % in a three-phase system. The devices are self-powered (measuring voltage = rated control supply voltage) and work on the closed-circuit principle.
3UG4.1 line monitoring relay 6.4 3UG4513 line monitoring relay Reset response The device features an autoreset that resets the output relays to their original state after an error message and rectification of the fault that has occurred.
3UG4.1 line monitoring relay 6.4 3UG4513 line monitoring relay 6.4.3 Operation Parameters The following parameters can be set on the relevant rotary button using a screwdriver: Table 6- 2 Parameter information, 3UG4513 line monitoring relay Parameters Control element 1) Setting range Increment Minimum value Maximum value Tripping delay time (Delay) 3 0.
3UG4.1 line monitoring relay 6.4 3UG4513 line monitoring relay 6.4.4 Diagnostics 6.4.4.
3UG4.1 line monitoring relay 6.4 3UG4513 line monitoring relay 6.4.5 Circuit diagrams Internal circuit diagrams 3UG4513 / / / 8* Figure 6-1 3UG4513 line monitoring relay Note It is not necessary to fuse the measuring circuit to protect the device. Fusing for line protection depends on the cross-section used.
3UG4.1 line monitoring relay 6.4 3UG4513 line monitoring relay 6.4.6 Technical data Measuring circuit 3UG4513-..... Type of voltage for monitoring AC Number of poles for main current circuit 3 Measurable voltage • for AC Adjustable voltage range V 160 … 690 V 200 … 690 General technical details 3UG4513-.....
3UG4.1 line monitoring relay 6.4 3UG4513 line monitoring relay 3UG4513-.....
3UG4.1 line monitoring relay 6.4 3UG4513 line monitoring relay 3UG4513-.....
3UG4.1 line monitoring relay 6.4 3UG4513 line monitoring relay 3UG4513-1.... 3UG4513-2.... Distance, to be maintained, conductive elements • forwards mm 0 • backwards mm 0 • sidewards mm 0 • upwards mm 0 • downwards mm 0 Type of mounting snap-on mounting Product function removable terminal for auxiliary and control circuit Yes Design of the electrical connection screw-type terminals spring-loaded terminals 1x (0.5 ... 4 mm2), 2x (0.5 ... 2.5 mm2) 2x (0.25 ... 1.
3UG4.1 line monitoring relay 6.5 3UG4614 line monitoring relay 6.5 3UG4614 line monitoring relay 6.5.1 Operator controls and connection terminals Front view / terminal labeling 3UG4614 Front view L1 Description L2 SIRIUS L3 3 ① Terminal block (removable): Connection is possible using screw terminals or spring-loaded terminals.
3UG4.1 line monitoring relay 6.5 3UG4614 line monitoring relay 6.5.2 Functions General functionality The 3UG4614 line monitoring relays monitor a three-phase system for phase asymmetry, undervoltage, phase failure, and phase sequence. The devices feature a wide-range voltage input and are self-powered (measuring voltage = rated control supply voltage).
3UG4.1 line monitoring relay 6.5 3UG4614 line monitoring relay Startup delay After applying the supply voltage or resetting the monitoring relays, the set ON-delay begins (onDel). During this time, undershooting or overshooting of the set threshold values will not cause the CO contact to respond but instead will result in a restart of the ON-delay.
3UG4.1 line monitoring relay 6.
3UG4.1 line monitoring relay 6.5 3UG4614 line monitoring relay 6.5.3 Operation Parameters Parameterization of the devices is possible locally using the display and the three keys.
3UG4.1 line monitoring relay 6.5 3UG4614 line monitoring relay 6.5.4 Diagnostics 6.5.4.1 Indications on the display Display information The display is divided into three different areas. 1 3 2 ① ② ③ Voltage measured value or fault symbol Type of monitoring Symbols of the change-over contacts Meaning of the information on the display Note Indications in the event of a fault The symbols on the display flash to indicate an error.
3UG4.1 line monitoring relay 6.
3UG4.1 line monitoring relay 6.5 3UG4614 line monitoring relay 6.5.5 Circuit diagrams Internal circuit diagrams 3UG4614 / / / 8* Figure 6-2 3UG4614 line monitoring relay Note It is not necessary to fuse the measuring circuit to protect the device. Fusing for line protection depends on the cross-section used.
3UG4.1 line monitoring relay 6.5 3UG4614 line monitoring relay 6.5.6 Technical data Measuring circuit 3UG4614-..... Type of voltage for monitoring AC Number of poles for main current circuit 3 Measurable voltage • for AC Adjustable voltage range V 160 … 690 V 120 … 690 Adjustable response delay time • when starting s 0.1 … 20 • with lower or upper limit violation s 0.1 … 20 General technical details 3UG4614-.....
3UG4.1 line monitoring relay 6.5 3UG4614 line monitoring relay 3UG4614-.....
3UG4.1 line monitoring relay 6.5 3UG4614 line monitoring relay 3UG4614-..... Galvanic isolation between entrance and outlet Yes Galvanic isolation between the outputs Yes Mechanical operating cycles as operating time typical 10 000 000 Electrical operating cycles as operating time at AC-15 at 230 V typical 100 000 Operating cycles with 3RT2 contactor maximum 1/h 5 000 Mechanical design 3UG4614-1.... Width mm 22.5 Height mm 92 Depth mm 91 Built in orientation 3UG4614-2....
3UG4.1 line monitoring relay 6.5 3UG4614 line monitoring relay Design of the electrical connection 3UG4614-1.... 3UG4614-2.... screw-type terminals spring-loaded terminals 1x (0,5 ... 4 mm2), 2x (0,5 ... 2,5 mm2) 2x (0.25 ... 1.5 mm2) 1x (0,5 ... 2,5 mm2), 2x (0,5 ... 1,5 mm2) — 2 x (0.25 ... 1.5 mm2) Type of the connectable conductor cross-section • solid • finely stranded • – with wire end processing – without wire end processing 2x (0.25 ... 1.
3UG4.1 line monitoring relay 6.6 3UG4615 / 3UG4616 line monitoring relays 6.6 3UG4615 / 3UG4616 line monitoring relays 6.6.1 Operator controls and connection terminals Front view / terminal labeling 3UG4615/ 3UG4616 Front view Description 3/N L1 L2 SIRIUS L3 3 Position digits 90-400VN ① Terminal block (removable) Connection is possible using screw-type terminals or spring-loaded terminals.
3UG4.1 line monitoring relay 6.6 3UG4615 / 3UG4616 line monitoring relays 6.6.2 Functions General functionality The 3UG4615 line monitoring relays monitor a three-phase system for phase failure, undervoltage, overvoltage, and phase sequence. Note The 3UG4616 line monitoring relays have the same functions as the 3UG4615 monitoring relays and also monitor the neutral conductor for failure.
3UG4.1 line monitoring relay 6.6 3UG4615 / 3UG4616 line monitoring relays Monitoring The 3UG4615 / 3UG4616 line monitoring relays have two output relays. With output relay K1, a three-phase system is monitored for undervoltage. With output relay K2, a threephase system is monitored for overvoltage. The output relays respond in accordance with the set relay switching behavior (closed-circuit principle NC or open-circuit principle NO).
3UG4.1 line monitoring relay 6.
3UG4.1 line monitoring relay 6.6 3UG4615 / 3UG4616 line monitoring relays 6.6.3 Operation Parameters Parameterization of the devices is possible locally using the display and the three keys.
3UG4.1 line monitoring relay 6.6 3UG4615 / 3UG4616 line monitoring relays 6.6.4 Diagnostics 6.6.4.1 Indications on the display Display information The display is divided into three different areas. 1 3 ① ② ③ 2 Voltage measured value or fault symbol Type of monitoring Symbols of the change-over contacts Meaning of the information on the display Note Indications in the event of a fault The symbols on the display flash to indicate an error.
3UG4.1 line monitoring relay 6.
3UG4.1 line monitoring relay 6.6 3UG4615 / 3UG4616 line monitoring relays 6.6.5 Circuit diagrams Internal circuit diagrams 3UG4615 / 3UG4616 3UG4615 3UG4616 / / / 1 / / 8* 8* 3UG4615 line monitoring relay / 3UG4616 line monitoring relay Note It is not necessary to fuse the measuring circuit to protect the device. Fusing for line protection depends on the cross-section used.
3UG4.1 line monitoring relay 6.6 3UG4615 / 3UG4616 line monitoring relays 6.6.6 Technical data Measuring circuit 3UG4615-..... Type of voltage for monitoring AC Number of poles for main current circuit 3 3UG4616-..... Measurable voltage V 160 … 690 Adjustable voltage range V 160 … 690 Adjustable response delay time with lower or upper limit violation s 0.1 … 20 • for AC General technical details 3UG4615-.....
3UG4.1 line monitoring relay 6.6 3UG4615 / 3UG4616 line monitoring relays 3UG4615-..... Type of voltage of the controlled supply voltage 3UG4616-.....
3UG4.1 line monitoring relay 6.6 3UG4615 / 3UG4616 line monitoring relays 3UG4615-..... Degree of pollution 3UG4616-.....
3UG4.1 line monitoring relay 6.6 3UG4615 / 3UG4616 line monitoring relays 3UG4615-1.... 3UG4616-1.... 3UG4615-2.... 3UG4616-2.... Distance, to be maintained, conductive elements • forwards mm 0 • backwards mm 0 • sidewards mm 0 • upwards mm 0 • downwards mm 0 Type of mounting snap-on mounting Product function removable terminal for auxiliary and control circuit Yes Design of the electrical connection screw-type terminals spring-loaded terminals 1x (0.5 ... 4 mm2), 2x (0.5 ...
3UG4.1 line monitoring relay 6.7 3UG4617 / 3UG4618 line monitoring relays 6.7 3UG4617 / 3UG4618 line monitoring relays 6.7.1 Operator controls and connection terminals Front view / terminal labeling 3UG4617 / 3UG4618 Front view Description 3/N L1 L2 SIRIUS Position digits 90-400VN L3 3 160-690V Del -> Umin/Umax/ Asym delay Mem ? -> Memory? 3UG4618-....
3UG4.1 line monitoring relay 6.7 3UG4617 / 3UG4618 line monitoring relays 6.7.2 Functions General functionality The 3UG4617 line monitoring relays monitor a three-phase system for phase sequence, phase failure, phase asymmetry, undervoltage, and overvoltage. Note The 3UG4618 line monitoring relays have the same functions as the 3UG4617 monitoring relays and also monitor the neutral conductor for failure.
3UG4.1 line monitoring relay 6.7 3UG4617 / 3UG4618 line monitoring relays Monitoring Output relay K1 is for warning or shutdown on faults in the power system (voltage, asymmetry). Output relay K2 responds differently depending on the phase sequence. Phase sequence If the correct phase sequence is applied to terminals L1-L2-L3, output relay K2 (relay contact 21-22-24) picks up. This is represented by a relay symbol on the display. If the phase sequence is incorrect, output relay K2 will not pick up.
3UG4.1 line monitoring relay 6.
3UG4.1 line monitoring relay 6.7 3UG4617 / 3UG4618 line monitoring relays 6.7.3 Operation Parameters Parameterization of the devices is possible locally using the display and the three keys.
3UG4.1 line monitoring relay 6.7 3UG4617 / 3UG4618 line monitoring relays 6.7.4 Diagnostics 6.7.4.1 Indications on the display Display information The display is divided into three different areas. 1 3 ① ② ③ 2 Voltage measured value or fault symbol Type of monitoring Symbols of the change-over contacts Meaning of the information on the display Note Indications in the event of a fault The symbols on the display flash to indicate an error.
3UG4.1 line monitoring relay 6.7 3UG4617 / 3UG4618 line monitoring relays Display area ③ Symbol Meaning Error ③ • Not flashing: Relay contact 11/12 open, relay contact 11/14 closed • Flashing: Delay time (tripping delay) is running • Masked out: Relay contact 11/12 closed, relay contact 11/14 open • Not flashing: Relay contact 21/22 open, relay contact 21/24 closed • Masked out: Relay contact 21/22 closed, relay contact 21/24 open Note CO contact 1 switches on all types of error.
3UG4.1 line monitoring relay 6.7 3UG4617 / 3UG4618 line monitoring relays 6.7.5 Circuit diagrams 6.7.5.1 Internal circuit diagrams Internal circuit diagram 3UG4617 / 3UG4618 3UG4617 3UG4618 / / / 1 / / / 8* 8* 3UG4617 line monitoring relay 3UG4618 line monitoring relay Note It is not necessary to fuse the measuring circuit to protect the device. Fusing for line protection depends on the cross-section used. 6.7.5.
3UG4.1 line monitoring relay 6.7 3UG4617 / 3UG4618 line monitoring relays 6.7.6 Technical data Measuring circuit 3UG4617-..... Type of voltage for monitoring AC Number of poles for main current circuit 3 3UG4618-..... Measurable voltage V 160 … 690 Adjustable voltage range V 160 … 690 Adjustable response delay time with lower or upper limit violation s 0.1 … 20 • for AC General technical details 3UG4617-.....
3UG4.1 line monitoring relay 6.7 3UG4617 / 3UG4618 line monitoring relays 3UG4617-..... Type of voltage of the controlled supply voltage 3UG4618-.....
3UG4.1 line monitoring relay 6.7 3UG4617 / 3UG4618 line monitoring relays 3UG4617-..... Degree of pollution 3UG4618-.....
3UG4.1 line monitoring relay 6.7 3UG4617 / 3UG4618 line monitoring relays 3UG4617-1.... 3UG4618-1.... 3UG4617-2.... 3UG4618-2.... Distance, to be maintained, conductive elements • forwards mm 0 • backwards mm 0 • sidewards mm 0 • upwards mm 0 • downwards mm 0 Type of mounting snap-on mounting Product function removable terminal for auxiliary and control circuit Yes Design of the electrical connection screw-type terminals spring-loaded terminals 1x (0.5 ... 4 mm2), 2x (0.5 ...
3UG4621/3UG4622 current monitoring relays 7.
3UG4621/3UG4622 current monitoring relays 7.2 Operator controls and connection terminals 7.
3UG4621/3UG4622 current monitoring relays 7.3 Functions 7.3 Functions General functionality Depending on the set threshold, the 3UG4621 / 3UG4622 current monitoring relays monitor a single-phase AC load current (RMS value) or DC load current flowing over terminals IN and M of the device for overshoot (I▲) or undershoot (I▼) or in range monitoring (I▲ and I▼). The devices differ by their measuring ranges and versions with different rated control supply voltages.
3UG4621/3UG4622 current monitoring relays 7.3 Functions Relay switching behavior The relay switching behavior can be defined in order to adapt the current monitoring relay to different external circuit connections and applications. If the closed-circuit principle (NC) is set, active switching of the relay when no fault is pending also ensures that a power failure is detected as a fault.
3UG4621/3UG4622 current monitoring relays 7.
3UG4621/3UG4622 current monitoring relays 7.
3UG4621/3UG4622 current monitoring relays 7.4 Operation 7.4 Operation Parameters Parameterization of the devices is possible locally using the display and the three keys.
3UG4621/3UG4622 current monitoring relays 7.5 Diagnostics Note Deactivating monitoring If the upper and lower threshold values are deactivated (OFF), monitoring will cease for: • Current overshoot • Current undershoot The up-to-date measured value is displayed permanently. The parameters are described in Chapter "Parameters (Page 351)." Menu-based operation is described in Chapter "Menu-based operation (Page 36)." 7.5 Diagnostics 7.5.
3UG4621/3UG4622 current monitoring relays 7.5 Diagnostics The following statuses and faults are indicated on the display as a diagnostics message with flashing symbols: Display areas ① Symbol 5.
3UG4621/3UG4622 current monitoring relays 7.6 Circuit diagrams 7.6 Circuit diagrams 7.6.1 Internal circuit diagrams Internal circuit diagrams 3UG4621 / 3UG4622 ,1 $ $ ,! 0 Figure 7-1 3UG4621/3UG4622 current monitoring relays Note On the 24 V AC / DC version of the 3UG4621/22-.AA30, terminals A2 and M (GND) are electrically connected in the device! The load current must flow through terminal M (GND). On the 24 to 240 V AC/DC versions of the 3UG4621/22-.
3UG4621/3UG4622 current monitoring relays 7.6 Circuit diagrams 7.6.2 Wiring examples Wiring examples Note If this arrangement is not complied with, the monitoring relay may be destroyed and the short-circuit current may damage the plant! 3UG46..-.AW30 Single-phase operation Three-phase operation AC/DC AC/DC Uload Load A1 IN 11 < > A2 12 14 M L1 A1 IN < > A2 L2 L3 11 12 14 M Mload Load 3UG462.-.AW30 single-phase operation 3UG462.-.AW30 three-phase operation 3UG462.-.
3UG4621/3UG4622 current monitoring relays 7.6 Circuit diagrams • three-phase o.k. o.k. L1 L2 L3 24 V AC/DC A1 A1 IN < > L1 24 V AC/DC L2 L3 IN < > A2 M M A2 load load Operation with a common control circuit and load current circuit • single-phase o.k. o.k. 24 V AC/DC 24 V AC/DC Load A1 IN 11 < > Load IN < > 12 optional A2 A1 M 14 A2 M Note Configuration In the case of 3UG462.-.
3UG4621/3UG4622 current monitoring relays 7.7 Technical data 7.7 Technical data Measuring circuit 3UG4621-..A Number of poles for main current circuit 1 Type of current for monitoring AC/DC 3UG4621-..W 3UG4622-..A Measurable current A 0.003 … 0.6 0.05 … 15 Measurable current for AC A 0.003 … 0.6 0.05 … 15 Measurable line frequency Hz 40 … 500 Internal resistance of the measuring circuit Ω 0.5 0.005 3UG4622-..W Adjustable response current • 1 A 0.003 … 0.5 0.5 … 10 • 2 A 0.
3UG4621/3UG4622 current monitoring relays 7.7 Technical data General technical details 3UG4621-..A.. 3UG4622-..A.. Product function Current monitoring relay Design of the display LCD 3UG4621-..W.. 3UG4622-..W..
3UG4621/3UG4622 current monitoring relays 7.7 Technical data 3UG4621-..A.. 3UG4622-..A.. 3UG4621-..W.. 3UG4622-..W..
3UG4621/3UG4622 current monitoring relays 7.7 Technical data 3UG4621-..A.. 3UG4622-..A.. 3UG4621-..W..
3UG4621/3UG4622 current monitoring relays 7.7 Technical data 3UG4621-..A.. Electrical operating cycles as operating time at AC-15 at 230 V typical Operating cycles with 3RT2 contactor maximum 3UG4622-..A.. 3UG4621-..W.. 3UG4622-..W.. 3UG4622-1.... 3UG4621-2.... 3UG4622-2.... 100 000 1/h 5 000 Mechanical design 3UG4621-1.... Width mm 22.
3UG4621/3UG4622 current monitoring relays 7.7 Technical data 3UG4621-1.... 3UG4622-1.... 3UG4621-2.... 3UG4622-2....
3UG4624 residual current monitoring relay 8.
3UG4624 residual current monitoring relay 8.2 Operator controls and connection terminals 8.2 Operator controls and connection terminals Front view / terminal labeling 3UG4624 Front view Description C1 Position digits C2 Lx 90--690V Ly/N SIRIUS I n -> Rated fault current onDel -> Power on delay I Del -> Imax delay Mem ? -> Memory? NC -> Circuit principle ① Terminal block (removable): Connection is possible using screw terminals or spring-loaded terminals.
3UG4624 residual current monitoring relay 8.3 Functions 8.3 Functions General functionality The 3UG4624 fault current monitoring relays are powered with a rated control supply voltage of 90 to 690 V AC (rms value), 50 / 60 Hz through terminals Lx and Ly / N. The 3UG4624 residual current monitoring relays have a display and are parameterized with three keys. You will find the setting ranges and factory settings of the available parameters in Chapter "Operation (Page 177).
3UG4624 residual current monitoring relay 8.3 Functions Monitoring If the measured residual current exceeds the set warning threshold (I!), the associated CO contact 21-22-24 changes the switching state without delay and a (!) appears on the display as an indication. If the measured fault current exceeds the set threshold (I▲), the set delay time (I▲Del) starts and the associated relay symbol flashes. After this time has expired, the associated CO contact 11-12-14 changes the switching state.
3UG4624 residual current monitoring relay 8.3 Functions Summation current transformers The 3UL22 summation current transformer can be used together with the 3UG4624 residual current monitoring relay to acquire residual currents in machines and plants. These necessary accessories are described in Chapter "Summation current transformer for the 3UG4624 monitoring relay (Page 320).
3UG4624 residual current monitoring relay 8.
3UG4624 residual current monitoring relay 8.4 Operation 8.4 Operation Parameters Parameterization of the devices is possible locally using the display and the three keys.
3UG4624 residual current monitoring relay 8.4 Operation Display of the current residual current by rms value setting The 3UL22 summation current transformer used with its stated residual current rating is chosen in menu "SET" as the setting value IΔn from 0.3 to 40 A in the 8 fixed steps that are possible.
3UG4624 residual current monitoring relay 8.5 Diagnostics 8.5 Diagnostics 8.5.1 Indication on the display Display information The display is divided into three different areas. 1 3 2 ① ② ③ Current measured value or fault symbol Type of monitoring Symbols of the change-over contacts Meaning of the information on the display Note Indications in the event of a fault The symbols on the display flash to indicate an error.
3UG4624 residual current monitoring relay 8.6 Circuit diagrams 8.5.2 Reset RESET How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset response (Page 351)"). The following settings can be selected: ● Automatic reset (Memory = O / Mem = no) The device is reset automatically as soon as a previously occurring error has been dealt with.
3UG4624 residual current monitoring relay 8.6 Circuit diagrams 8.6.2 Wiring examples L1 L2 L3 N F1 T1 24 V AC S1 (Test) R1 Lx Ly/N C1 3UL22.. Z1 Z3 R2 3UG4624 C2 Z2 A2 load Figure 8-2 Wiring example of 3UG4624 with 3UL22 IΔn 3UL22013UL22023UL2203-1A 0.3 A -2A 0.
3UG4624 residual current monitoring relay 8.6 Circuit diagrams Table 8- 4 3UL22 summation current transformers for external ground-fault monitoring Detection of fault current in machines and plants Rated insulation voltage Ui Rated residual current IΔn Bushing opening diameter For Protodur cable (push-through) Order number 690 V AC 0.3 A 40 mm max. 4 x 95 mm2 3UL2201-1A 0.5 A 3UL2201-2A 1A 690 V AC 0.3 A 3UL2201-3A 65 mm max.
3UG4624 residual current monitoring relay 8.7 Technical data 8.7 Technical data Measuring circuit 3UG4624-..... Type of current for monitoring Measurable line frequency AC Hz 60 … 50 Adjustable response current • 1 A 0.03 … 40 • 2 A 0.03 … 40 Adjustable response delay time • when starting s 0.1 … 20 • with lower or upper limit violation s 0.
3UG4624 residual current monitoring relay 8.7 Technical data 3UG4624-.....
3UG4624 residual current monitoring relay 8.7 Technical data 3UG4624-..... Design of the electrical isolation galvanic Galvanic isolation • between entrance and outlet Yes • between the outputs Yes • between the voltage supply and other circuits Yes Mechanical operating cycles as operating time typical 10 000 000 Electrical operating cycles as operating time at AC-15 at 230 V typical 100 000 Operating cycles with 3RT2 contactor maximum 1/h 5 000 Mechanical design 3UG4624-1....
3UG4624 residual current monitoring relay 8.7 Technical data 3UG4624-1.... 3UG4624-2.... Type of mounting screw and snap-on mounting onto 35 mm standard mounting rail Product function removable terminal for auxiliary and control circuit Yes Design of the electrical connection screw-type terminals spring-loaded terminals 1x (0.5 ... 4 mm2), 2x (0.5 ... 2.5 mm2) 2x (0.25 ... 1.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.2 Operator controls and connection terminals 9.2 Operator controls and connection terminals 3UG4625 front view/terminal labeling Front view Description C1 A1+ Position digits C2 24-240V AC/DC A2- SIRIUS ① Terminal block (removable): Connection is possible using screw terminals or spring-loaded terminals.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.3 Functions 9.3 Functions General functionality 3UG4625 residual current monitoring relays are supplied with a rated control supply voltage of 24 to 240 V AC/DC (rms value), 50/60 Hz via terminals A1+ and A2-. 3UG4625 residual current monitoring relays are equipped with a display and are parameterized with three keys. You will find the setting ranges and factory settings of the available parameters in Chapter "Operation (Page 196)".
3UG4625 residual current monitoring relay with 3UL23 transformer 9.3 Functions ● Wide-range supply voltage 3UG4625 residual current monitoring relays can be operated at an input voltage of between 24 and 240 V AC/DC. This not only ensures that devices can be used worldwide, but that temporary supply voltage dips do not cause a failure of the monitoring function, that is, plant stoppage.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.3 Functions Limits of fault current measurement In the event of increasing primary currents, transformer production tolerances, imbalances in the cable routing and current loads in individual cables increasingly cause what appear to be fault currents that are detected by the evaluation units. An increased false tripping may occur if excessively low monitoring limit values have been set at high primary currents.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.3 Functions The monitored current waveforms also have a strong influence on the measuring accuracy. In the case of loads with generalized phase control, deviations from the measuring accuracy can occur when monitoring for high residual current limits. The cause of this is the extreme difference between the monitored rms values and the peak values of the residual current.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.3 Functions Tripping delay If the measured value exceeds the set threshold (I▲) after expiry of the ON-delay time (onDel), the set tripping delay time (I▲Del) starts and the relay symbol flashes. After expiry of this time, the output relay K1 changes the switching state. Exceeding the set warning threshold will cause output relay K2 to switch immediately without taking into account the tripping delay time.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.3 Functions Function diagrams for 3UG4625 Note Difference between Hyst and Hysteresis In the following diagrams, the term "Hyst" refers to the "Hysteresis" parameter. The "Hysteresis" parameter refers to the monitored limit values (I▲) and can be set in the SET menu. However, "Hyst = 5 %" refers to the warning thresholds (I!) and is permanently set to 5 %.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.3 Functions Display Memory = yes Relay switching behavior = NC (closed-circuit principle) I▲ / I! A1-A2 Mem = yes Reset t > 2,5s I >I ! I I >I Hyst I! Hyst = 5 % I = 0.02A I=0 11/14 11/12 21/24 21/22 Init Display I onDel onDel Del onDel Memory = yes Relay switching behavior = NO (open-circuit principle) I▲ / I! Mem = yes A1-A2 Reset t > 2,5s I >I ! I I >I Hyst I! Hyst = 5 % I = 0.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.4 Operation 9.4 Operation Parameters Parameterization of the devices is possible locally using the display and the three keys.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.5 Diagnostics 9.5 Diagnostics 9.5.1 Indications on the display Display information The display is divided into three different areas. 1 3 2 ① ② ③ Current measured value or fault symbol Type of monitoring Symbols of the change-over contacts Meaning of the information on the display Note Indications in the event of a fault The symbols on the display flash to indicate an error.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.5 Diagnostics Display area Symbol Meaning ① , Measurement range exceeded (> 40 A) ① 0.00A Fallen below measurement range ① Open-circuit ① Short-circuit You will find more information about the switching behavior of the output relay in Chapter "Functions (Page 189)." 9.5.2 Reset RESET How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset response (Page 351)").
3UG4625 residual current monitoring relay with 3UL23 transformer 9.6 Circuit diagrams 9.6 Circuit diagrams 9.6.1 Internal circuit diagrams 3UG4625 internal circuit diagrams $ & & $ Figure 9-1 3UG4625-.CW30 residual current monitoring relay, 24 to 240 V Note 3UG4625 residual current monitoring relays are suitable for operation with 3UL23 residual current transformers for external ground-fault monitoring.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.6 Circuit diagrams 9.6.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.7 Technical data 9.7 Technical data Measuring circuit 3UG4625-..... Type of current for monitoring Measurable line frequency AC Hz 16 400 Adjustable response current • 1 A 0.03 … 40 • 2 A 0.03 … 40 Adjustable response delay time when starting s 0.1 … 20 Adjustable response delay time s 0.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.7 Technical data 3UG4625-..... Type of voltage of the controlled supply voltage AC/DC Control supply voltage • at 50 Hz at AC – • V 24 … 240 V 24 … 240 V 24 … 240 at 60 Hz at AC – • rated value rated value for DC – rated value Working range factor supply voltage rated value • at 50 Hz – • at 60 Hz – • 0.85 … 1.1 for AC 0.85 … 1.1 for AC 0.85 … 1.
3UG4625 residual current monitoring relay with 3UL23 transformer 9.7 Technical data 3UG4625-.....
3UG4625 residual current monitoring relay with 3UL23 transformer 9.7 Technical data 3UG4625-1.... 3UG4625-2....
3UG458. insulation monitoring relay. 10 Overview The 3UG458. insulation monitoring relays are used for monitoring the insulation resistance (in accordance with IEC 61557-8) between ungrounded single-phase or three-phase AC systems and a protective conductor. The family comprises the following devices: ● Insulation monitoring relays for ungrounded AC systems with a rated system voltage of up to Un = 400 V AC.
3UG458. insulation monitoring relay. 10.1 Application areas 10.1 Application areas Application areas The 3UG458.
3UG458. insulation monitoring relay. 10.2 Performance features of the insulation monitoring relays 10.2 Performance features of the insulation monitoring relays General data Table 10- 3 General data of the 3UG4581/3UG4582/3UG4583 insulation monitoring relays General data Insulation monitoring relays 3UG4581 3UG4582 3UG4583 Setting range of the target pick-up values • 1 to 100 kΩ ✓ ✓ ✓ • 2 to 200 kΩ — — ✓ Rated voltage of the system to be monitored • 0 ... 250 V AC — ✓ — • 0 ...
3UG458. insulation monitoring relay. 10.
3UG458. insulation monitoring relay. 10.3 3UG4581 insulation monitoring relay 10.3 3UG4581 insulation monitoring relay 10.3.1 Operator controls and connection terminals Front view/terminal labeling 3UG4581 Front view Description $ < < 7HVW 5HVHW 5 YDOXH N 5 5 5 ) 5 YDOXH N / ① Terminal block: Screw-type connections are possible.
3UG458. insulation monitoring relay. 10.3 3UG4581 insulation monitoring relay 10.3.2 Functions General functionality The 3UG4581 insulation monitoring relays are supplied with a rated control and supply voltage of 24 V to 240 V AC/DC, and they monitor the insulation resistance in ungrounded AC systems in accordance with IEC 61557-8. The devices can monitor control circuits (1-phase) and main circuits (3-phase).
3UG458. insulation monitoring relay. 10.3 3UG4581 insulation monitoring relay Monitoring The system to be monitored is connected to terminal L (connection to phase or N conductor). The ground potential is connected to terminal . The devices work according to the closed-circuit principle NC. After applying the rated control and supply voltage, the insulation monitoring relay goes through an internal test that checks the proper functioning of the operational device.
3UG458. insulation monitoring relay. 10.
3UG458. insulation monitoring relay. 10.
3UG458. insulation monitoring relay. 10.3 3UG4581 insulation monitoring relay 10.3.3 Operator control Parameters The following parameters can be set on the two ten-level rotary buttons (absolute scale) with the help of a screwdriver: Table 10- 4 Parameter information, 3UG4581 insulation monitoring relay Parameters Control elements 1) Setting range Minimum value Maximum value Threshold for undershoot (tens position of R) (R.1-value)2) 8 0 kΩ 90 kΩ 10 kΩ increments Threshold for undershoot (R.
3UG458. insulation monitoring relay. 10.3 3UG4581 insulation monitoring relay Carrying out the self-test The test function is only possible if there is no fault. By operating the combined test/reset button, the insulation monitoring relay goes through an internal test that checks the proper functioning of the operational device.
3UG458. insulation monitoring relay. 10.3 3UG4581 insulation monitoring relay 10.3.5 Circuit diagrams 10.3.5.1 Internal circuit diagrams Internal circuit diagram 3UG4581-1AW30 3UG4581-1AW30 / .
3UG458. insulation monitoring relay. 10.3 3UG4581 insulation monitoring relay Wiring examples 3UG4581 insulation monitoring relays Measuring input L can be connected to any conductor (phase or N conductor). The rated system voltage must be Un ≤ 400 V AC (50 to 60 Hz).
3UG458. insulation monitoring relay. 10.3 3UG4581 insulation monitoring relay Application examples The figure below shows monitoring for ground fault/insulation fault in the case of an ungrounded 2-wire IT AC system. The voltage source is the secondary side of an isolating transformer that galvanically isolates the system and the downstream circuit.
3UG458. insulation monitoring relay. 10.3 3UG4581 insulation monitoring relay The figure below shows monitoring for ground fault/insulation fault in the case of an ungrounded 4-wire IT AC system. The voltage source is the secondary side of an isolating transformer that galvanically isolates the system and the downstream circuit.
3UG458. insulation monitoring relay. 10.3 3UG4581 insulation monitoring relay 10.3.6 Characteristics Characteristic curves of the 3UG4581 insulation monitoring relays The characteristics below show the load limit curves of the 3UG4581 insulation monitoring relays.
3UG458. insulation monitoring relay. 10.
3UG458. insulation monitoring relay. 10.3 3UG4581 insulation monitoring relay 10.3.
3UG458. insulation monitoring relay. 10.3 3UG4581 insulation monitoring relay 3UG4581-1AW30 Ambient temperature • during operating °C -25 … +60 Item designation according to DIN EN 61346-2 K Item designation according to DIN 40719 extendable after IEC 2042 according to IEC 750 K Mechanical design 3UG4581-1AW30 Width mm 22.
3UG458. insulation monitoring relay. 10.3 3UG4581 insulation monitoring relay 3UG4581-1AW30 Design of the electrical connection screw-type terminals Conductor cross-section that can be connected • solid mm² 0.75 … 2.5 mm² 0.75 … 2.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays 10.4 3UG4582/3UG4583 insulation monitoring relays 10.4.1 Operator controls and connection terminals Front view/terminal labeling 3UG4582 Front view Description $ .( < < < s 8* $: 7HVW 5HVHW 5 YDOXH N 5 5 5 ) Position digits ① Terminal block: Screw-type connections are possible.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays Front view/terminal labeling 3UG4583 Front view Description $ < < < s 8* &: 5 YDOXH N 5 YDOXH N 7HVW 5HVHW 5[ 5[ 5[ ) 5 YDOXH N 5 YDOXH N 21 / 96 / .( 9 9 $ Position digits ① Terminal block: Screw-type connections are possible.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays You will find information on connecting in Chapter "Circuit diagrams (Page 243)". 10.4.2 Functions General functionality The 3UG4582/3UG4583 insulation monitoring relays are supplied with a rated control and supply voltage of 24 V to 240 V AC/DC, and they monitor the insulation resistance in accordance with IEC 61557-8 in ungrounded IT-AC systems, IT-AC systems with galvanically connected DC circuits, or IT-DC systems.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays Monitoring The system to be monitored is connected to the measuring signal inputs L+, L-. The terminals can be connected to any conductor (phase, +/- potential, or N conductor). The measuring signal inputs must be connected to different conductors. The ground potential is connected to the terminals and KE.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays In the functional principle 2 x 1 changeover contacts, output relay K1 responds to threshold R1 (shutdown) and output relay K2 responds to threshold R2 (warning). If the measured value undershoots the set threshold R2 (warning), output relay K2 switches. If the measured value undershoots the set threshold R1 (shutdown), output relay K1 switches.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays Reset response and memory function The device features an autoreset that resets output relay K1 to its original state after an fault message and rectification of the fault that has occurred. As well as autoreset, the devices can also be set to manual RESET by means of external switching.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays Non-volatile memory function on the 3UG4583 The 3UG4583 insulation monitoring relays also have a configurable non-volatile (retentive) fault storage function. After shutting down and restoring the rated control and supply voltage, the device is in the state it was in prior to shutdown, until it is reset.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays 10.4.2.
3UG458. insulation monitoring relay. 10.
3UG458. insulation monitoring relay. 10.
3UG458. insulation monitoring relay. 10.
3UG458. insulation monitoring relay. 10.
3UG458. insulation monitoring relay. 10.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays 10.4.3 Operator control Parameters The following parameters can be set on the two (3UG4582) or four (3UG4583) ten-level rotary buttons (absolute scale) with the help of a screwdriver: Table 10- 5 Parameter information, 3UG4582/3UG4583 insulation monitoring relays Parameters Control elements 1) Setting range Minimum value Maximum value Threshold for undershoot (R.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays DIP switch The DIP switches are located behind the label on the front of the 3UG4583 insulation monitoring relays. Four settings can be parameterized with the DIP switch. The tables below contain the setting options on the device and the explanations for the relevant switch positions. When the device is delivered, the switch is in the position OFF.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays Table 10- 7 Definitions of the DIP switch positions - 3UG4583 DIP switch ON OFF Position 4 Functional principle 2 x 1 changeover contacts / 1 x 2 changeover contacts 2 x 1 changeover contacts 1 x 2 changeover contacts If functional principle 2 x 1 changeover contacts is set, output relay K1 responds to threshold R1 (shutdown) and output relay K2 responds to threshold R2 (warning).
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays Carrying out the self-test The test function is only possible if there is no fault. By operating the combined test/reset button, the insulation monitoring relay goes through an internal test that checks the proper functioning of the operational device.
3UG458. insulation monitoring relay. 10.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays 10.4.5 Circuit diagrams 10.4.5.1 Internal circuit diagrams Internal circuit diagrams 3UG4582-1AW30/3UG4583-1CW30 3UG4582-1AW30 / . / .( < < < $ N˖ $ Figure 10-10 3UG4582-1AW30 insulation monitoring relay 3UG4583-1CW30 / . / .
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays 10.4.5.2 Wiring examples Wiring examples 3UG4582 insulation monitoring relays Measuring inputs L+ and L- can be connected to any conductor (phase or N conductor). Measuring inputs L+ and L- must always be connected to different conductors. The rated system voltage is Un ≤ 250 V AC (15 to 400 Hz) or Un ≤ 300 V DC. 2-wire AC system / 2-wire DC system 2-wire AC system 2-wire DC system $ < < .
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays Application examples The figure below shows monitoring for ground fault/insulation fault in the different load circuits. / / / 1 3( $ < < .( < 8* $: / / $ $ < < 8* $: / / 0 a ① ② ③ ④ .( < $ The voltage source is the secondary side of an isolating transformer that galvanically isolates the system and the downstream circuit.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays Wiring examples 3UG4583 insulation monitoring relays Measuring inputs L+ and L- can be connected to any conductor (phase or N conductor). Measuring inputs L+ and L- must always be connected to different conductors. The rated system voltage is Un ≤ 400 V AC (15 to 400 Hz) or Un ≤ 600 V DC. The 3UG49831A upstream module must be used to monitor systems with higher voltages.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays Application examples The figure below shows monitoring for ground fault/insulation fault in the case of an ungrounded 4-wire AC system. / / / 1 3( $ < < < 8* &: / 9 9 9 / .( $ 0 a ① Loads Figure 10-13 Monitoring for ground fault/insulation fault in the case of an ungrounded 4-wire AC system Note The maximum cable length of the control cables is 50 m or 100 pF/m.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays / / / 1 3( $ < < < $ < < < 8* &: 8* &: / 96 9 9 / .( $ / 9 9 9 / . $ 0 a ① ② ③ ④ The voltage source is the secondary side of an isolating transformer that galvanically isolates the system and the downstream circuit. The insulation resistance of this motor feeder is always monitored when the motor is switched off.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays 10.4.6 Characteristics Characteristics of the 3UG4582 insulation monitoring relays The characteristics below show the load limit curves of the 3UG4582 insulation monitoring relays.
3UG458. insulation monitoring relay. 10.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays Characteristics of the 3UG4583 insulation monitoring relays The characteristics below show the load limit curves of the 3UG4583 insulation monitoring relays.
3UG458. insulation monitoring relay. 10.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays 10.4.7 Technical data 10.4.7.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays 3UG4582-1AW30 Working range factor supply voltage rated value • for DC • at 50 Hz – • 0.85 … 1.1 0.85 … 1.1 for AC at 60 Hz – 0.85 … 1.
3UG458. insulation monitoring relay. 10.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays 10.4.7.
3UG458. insulation monitoring relay. 10.
3UG458. insulation monitoring relay. 10.4 3UG4582/3UG4583 insulation monitoring relays 3UG4583-1CW30 Type of mounting snap-on fastening on 35 mm standard rail Product function removable terminal for auxiliary and control circuit No Design of the electrical connection screw-type terminals Conductor cross-section that can be connected • solid • finely stranded – with wire end processing mm² 0.75 … 2.5 mm² 0.75 … 2.
3UG463. voltage monitoring relay 11.
3UG463. voltage monitoring relay 11.2 3UG4631 / 3UG4632 voltage monitoring relay 11.2 3UG4631 / 3UG4632 voltage monitoring relay 11.2.1 Operator controls and connection terminals Front view / terminal labeling 3UG4631 / 3UG4632 Front view Description A1+ 24-240V IN SIRIUS M 1 ① Terminal block (removable): Connection is possible using screw terminals or spring-loaded terminals.
3UG463. voltage monitoring relay 11.2 3UG4631 / 3UG4632 voltage monitoring relay 11.2.2 Functions General functionality Depending on the setting, the 3UG4631 / 3UG4632 voltage monitoring relays are powered with a rated control supply voltage of 24 V AC/DC or 24 to 240 AC/DC and monitor an AC voltage or DC voltage at terminals IN and M of the device for overshoot (U▲) or undershoot (U▼) or in range monitoring (U▲ and U▼).
3UG463. voltage monitoring relay 11.
3UG463. voltage monitoring relay 11.3 3UG4633 voltage monitoring relay 11.3 3UG4633 voltage monitoring relay 11.3.1 Operator controls and connection terminals Front view / terminal assignment 3UG4633 Front view Description A1+ 12-275V SIRIUS 1 ① Terminal block (removable): Connection is possible using screw terminals or spring-loaded terminals.
3UG463. voltage monitoring relay 11.3 3UG4633 voltage monitoring relay 11.3.2 Functions General functionality Depending on the setting, the 3UG4633 voltage monitoring relays are self-powered (measuring voltage = rated control supply voltage) and monitor an AC voltage or DC voltage at terminals A1 and A2 of the device for overshoot (U▲) or undershoot (U▼) or in range monitoring (U▲ and U▼).
3UG463. voltage monitoring relay 11.
3UG463. voltage monitoring relay 11.4 Operation 11.4 Operation Parameters Parameterization of the devices is possible locally using the display and the three keys. Parameter information The table below shows the settable parameter information of the 3UG463. voltage monitoring relays: Table 11- 2 Menu level Parmeter information, 3UG463. voltage monitoring relays with digital setting Parameters Setting range Minimum value Factory setting Maximum value "RUN" Threshold for undershoot (U▼) 0.
3UG463. voltage monitoring relay 11.5 Diagnostics Note Deactivating monitoring If the upper and lower threshold values are deactivated (OFF), monitoring will cease for: • Voltage overshoot • Voltage undershoot The up-to-date measured value is displayed permanently. The parameters are described in Chapter "Parameters (Page 351)." Menu-based operation is described in Chapter "Menu-based operation (Page 36)." 11.5 Diagnostics 11.5.
3UG463. voltage monitoring relay 11.5 Diagnostics Meaning of the information on the display Note Indications in the event of a fault The symbols on the display flash to indicate an error. The following statuses and faults are indicated on the display as a diagnostics message with flashing symbols: Display area ① Symbol 20.
3UG463. voltage monitoring relay 11.5 Diagnostics 11.5.2 Reset RESET How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset response (Page 351)"). The following settings can be selected: ● Automatic reset (Memory = O / Mem = no) The device is reset automatically as soon as a previously occurring error has been dealt with.
3UG463. voltage monitoring relay 11.6 Circuit diagrams 11.6 Circuit diagrams 11.6.1 Internal circuit diagrams Internal circuit diagrams 3UG4631 / 3UG4632 and 3UG4633 3UG4631 / 3UG4632 ,1 3UG4633 $ $ $ $ 8! 0 8! 3UG4631 / 3UG4632 voltage monitoring relay 3UG4633 voltage monitoring relay Note On the 24 V AC/DC versions of the 3UG4631-.AA30 and 3UG4632-.
3UG463. voltage monitoring relay 11.6 Circuit diagrams 11.6.2 Wiring examples 3UG4631-.AA30 / 3UG4632-.AA30 AC/DC U Last A1(+) IN(+) 11 12 14 A2(–) Figure 11-1 M(–) 3UG4631-.AA30 / 3UG4632-.AA30 3UG4631-.AW30 / 3UG4632-.AW30 AC/DC U Last A1(+) IN(+) 11 12 14 A2(–) M(–) Figure 11-2 3UG4631-.AW30 / 3UG4632-.
3UG463. voltage monitoring relay 11.7 Technical data 11.7 Technical data Measuring circuit 3UG4631-1 Type of voltage for monitoring AC/DC Number of poles for main current circuit 1 Measurable line frequency Hz 500 … 40 3UG4632-1 3UG4633-1 3UG4631-2 3UG4632-2 3UG4633-2 40 … 500 Measurable voltage • for AC V 0.1 … 60 10 … 600 17 … 275 0.1 … 60 10 … 600 17 … 275 • for DC V 0.1 … 60 10 … 600 17 … 275 0.1 … 60 10 … 600 17 … 275 V 0.1 … 60 10 … 600 17 … 275 0.
3UG463. voltage monitoring relay 11.7 Technical data General technical details 3UG463.-1.A 3UG463.-1.L Product function Voltage monitoring relay Design of the display LCD 3UG463.1.W 3UG463.-2.A 3UG463.-2.L 3UG463.2.
3UG463. voltage monitoring relay 11.7 Technical data 3UG463.-1.A Precision of digital display 3UG463.-1.L 3UG463.1.W 3UG463.-2.A 3UG463.-2.L 3UG463.2.W +/-1 digit Relative temperature-related measurement deviation % 0.
3UG463. voltage monitoring relay 11.7 Technical data 3UG463.-1.A 3UG463.-1.L 3UG463.1.W Resistance against shock according to IEC 60068-2-27 sinusoidal half-wave 15g / 11 ms Installation altitude m at a height over sea level maximum 2 000 3UG463.-2.A 3UG463.-2.L 3UG463.2.
3UG463. voltage monitoring relay 11.7 Technical data 3UG463.-1.A 3UG463.-1.L 3UG463.1.W 3UG463.-2.A 3UG463.-2.L 3UG463.2.
3UG463. voltage monitoring relay 11.7 Technical data Mechanical design 3UG463.-1.... Width mm 22.5 Height mm 92 Depth mm 91 Built in orientation 3UG463.-2....
3UG463. voltage monitoring relay 11.7 Technical data Design of the electrical connection 3UG463.-1.... 3UG463.-2.... screw-type terminals spring-loaded terminals 1x (0.5 ... 4 mm2), 2x (0.5 ... 2.5 mm2) 2x (0.25 ... 1.5 mm2) Type of the connectable conductor cross-section • solid • finely stranded • – with wire end processing 1x (0.5 ... 2.5 mm2), 2x (0.5 ... 1.5 mm2) 2 x (0.25 ... 1.5 mm2) – without wire end processing — 2x (0.25 ... 1.5 mm2) for AWG conductors – solid 2x (20 ...
3UG4641 cos phi and active current monitoring relay 12.
3UG4641 cos phi and active current monitoring relay 12.2 Operator controls and connection terminals 12.2 Operator controls and connection terminals Front view / terminal labeling 3UG4641 Front view Description Lx 90--690V Ly/N IN ① Terminal block (removable): Connection is possible using screw terminals or spring-loaded terminals.
3UG4641 cos phi and active current monitoring relay 12.3 Functions 12.3 Functions General functionality The 3UG4641 cos phi and active current monitoring relays are self-powered (measuring voltage = rated control supply voltage) and monitor the power factor value in one phase (PF: power factor) and the resulting active current Ires (I resistive), for overshoot(φ▲ / Ires▲), undershoot (φ▼ / Ires▼) or range monitoring (φ▲ and φ▼ / Ires▲ and Ires▼) depending on the setting.
3UG4641 cos phi and active current monitoring relay 12.3 Functions Tripping delay If the measured value overshoots or undershoots the set threshold after expiry of the ONdelay time (onDel), the set tripping delay time (Del) and the relay symbol will flash. After expiry of this time, the output relays change the switching state. On the display, the current measuring value and the symbol for undershoot or overshoot flash.
3UG4641 cos phi and active current monitoring relay 12.
3UG4641 cos phi and active current monitoring relay 12.3 Functions Function diagrams 3UG4641 (cos phi monitoring) Display Memory = no Memory = no Relay switching behavior = NC (closed-circuit principle) Relay switching behavior = NO (open-circuit principle) φ> > φ = off PF > ϕ ϕ PF = 0 PF > ϕ Hyst, 0.10 cos ϕ = 0 ϕ PF = 0 11/14 11/12 11/14 11/12 21/24 21/22 21/24 21/22 onDel Del Hyst, 0.10 cos ϕ = 0 onDel Del φ > = off > φ PF < ϕ PF = 0 PF < ϕ Hyst, 0.
3UG4641 cos phi and active current monitoring relay 12.4 Operation 12.4 Operation Parameters Parameterization of the devices is possible locally using the display and the three keys.
3UG4641 cos phi and active current monitoring relay 12.5 Diagnostics 12.5 Diagnostics 12.5.1 Indications on the display Display information The display is divided into three different areas. 1 3 ① ② ③ 2 Current measuring value / cos phi measuring value or error symbol Type of monitoring Symbols of the change-over contacts Meaning of the information on the display Note Indications in the event of a fault The symbols on the display flash to indicate an error.
3UG4641 cos phi and active current monitoring relay 12.
3UG4641 cos phi and active current monitoring relay 12.6 Circuit diagrams 12.6 Circuit diagrams 12.6.1 Internal circuit diagrams Internal circuit diagrams 3UG4641 /[ /\ 1 ,1 FRV SKL! Figure 12-1 12.6.
3UG4641 cos phi and active current monitoring relay 12.
3UG4641 cos phi and active current monitoring relay 12.7 Technical data 12.7 Technical data Measuring circuit 3UG4641 Number of poles for main current circuit 2 Phase number Adaptable response value phase angle 1 ° Type of current for monitoring 0.1 … 0.99 AC Measurable current A 0.2 … 10 Adjustable response current 1 A 0.2 … 10 Adjustable response current 2 A 0.2 … 10 Adjustable response delay time • when starting s 0 … 99 • with lower or upper limit violation s 0.
3UG4641 cos phi and active current monitoring relay 12.7 Technical data 3UG4641-.....
3UG4641 cos phi and active current monitoring relay 12.7 Technical data 3UG4641-.....
3UG4641 cos phi and active current monitoring relay 12.7 Technical data 3UG4641-1.... 3UG4641-2.... Distance, to be maintained, conductive elements • forwards mm 0 • backwards mm 0 • sidewards mm 0 • upwards mm 0 • downwards mm 0 Type of mounting snap-on mounting Product function removable terminal for auxiliary and control circuit Yes Design of the electrical connection screw-type terminals spring-loaded terminals 1x (0.5 ... 4 mm2), 2x (0.5 ... 2.5 mm2) 2x (0.25 ... 1.
3UG4641 cos phi and active current monitoring relay 12.
13 3UG4651 speed monitoring relay 13.
3UG4651 speed monitoring relay 13.2 Operator controls and connection terminals 13.2 Operator controls and connection terminals Front view / terminal labeling 3UG4651 Front view Description 24V IN1 0V A1+ 24V EN RES Position digits SIRIUS rpm -> Revolutions/min Scale -> Pulses/revolution onDel -> Power on delay Mem ? -> Memory? NC -> Circuit principle ① Terminal block (removable): Connection is possible using screw terminals or spring-loaded terminals.
3UG4651 speed monitoring relay 13.3 Functions 13.3 Functions General functionality Depending on the setting, the speed monitoring relays monitor a speed in revolutions per minute (rpm) for overshoot (rpm▲), undershoot (rpm▼) or in range monitoring (rpm▲ and rpm▼). Depending on their design, the devices are powered with a rated control supply voltage of 24 V AC/DC or 24 to 240 V AC/DC supply voltage through terminals A1/A2.
3UG4651 speed monitoring relay 13.3 Functions Monitoring Startup delay To be able to start a drive, the output relay switches to the correct state during the ON-delay time (onDel) depending on the selected open-circuit principle or closed-circuit principle, even if the measured value is still under the set value. The ON-delay time is started either by switching on the rated control supply voltage or, if the rated control supply voltage is present, by actuating the relevant contact (e.g.
3UG4651 speed monitoring relay 13.
3UG4651 speed monitoring relay 13.4 Operation Note The relay control for the open-circuit principle NO is inverted to the represented function diagrams in the closed-circuit principle NC after application of the rated control supply voltage US. 13.4 Operation Parameters Parameterization of the devices is possible locally using the display and the three keys.
3UG4651 speed monitoring relay 13.5 Diagnostics 13.5 Diagnostics 13.5.1 Indications on the display Display information The display is divided into three different areas. 1 3 2 ① ② ③ Speed measured value or fault symbol Type of monitoring Symbol of the change-over contact Meaning of the information on the display Note Indications in the event of a fault The symbols on the display flash to indicate an error.
3UG4651 speed monitoring relay 13.5 Diagnostics 13.5.2 Reset RESET How the outputs are reset depends on the "Reset response" parameter (see Chapter "Reset response (Page 351)"). The following settings can be selected: ● Automatic reset (Memory = O / Mem = no) The device is reset automatically as soon as a previously occurring error has been dealt with.
3UG4651 speed monitoring relay 13.6 Circuit diagrams 13.6 Circuit diagrams 13.6.1 Internal circuit diagrams Internal circuit diagrams 3UG4651 + AC/DC U – pnp A1 (+) EN RES 24V 3UG46 51 IN1 0V 11 USP ! 12 A2 (–) IN2 14 8V2 AC/DC – NAMUR + 3UG4651-.AA30 24 V AC/DC 3UG4651-.AW30 24 to 240 V AC/DC Figure 13-1 3UG4651 speed monitoring relay Note On the 24 V AC/DC versions of the 3UG4651-.
3UG4651 speed monitoring relay 13.6 Circuit diagrams 13.6.2 Wiring examples Speed monitoring relays without Enable input AC/+U Reset S1 A1 (+) 3UG46 51 24V USP ! K1 IN1 BN I BU 0V IN2 12 14 NO NAMUR A2 (–) 11 K1 EN RES K2 8V2 AC/0V Speed monitoring relays with Enable input AC/+U S1 A1 (+) Enable Reset EN RES 3UG46 51 USP ! A2 (–) K1 IN2 S1 24V 1 IN1 4 0V 3 8V2 I NO DC 24V/ max.
3UG4651 speed monitoring relay 13.7 Technical data 13.7 Technical data Measuring circuit 3UG4651-..... Measurable line frequency Hz 50 … 60 Adjustable response delay time • when starting s 1 … 900 • with lower or upper limit violation s 0.1 … 99.9 1/min 0.1 … 2 200 Adjustable response value revolution Input voltage at the digital input 1 • initial value for signal<0>-recognition V 0 • final value for signal<0>-recognition V 1 • initial value for signal<1>-recognition V 4.
3UG4651 speed monitoring relay 13.7 Technical data General technical details 3UG4651-..A.. 3UG4651-..W..
3UG4651 speed monitoring relay 13.7 Technical data 3UG4651-..A.. 3UG4651-..W.. V 24 24 … 240 V 24 24 … 240 V 24 24 … 240 Control supply voltage • at 50 Hz at AC – • at 60 Hz at AC – • rated value rated value for DC – rated value Working range factor supply voltage rated value • at 50 Hz – • at 60 Hz – • 1.1 … 0.8 for AC 1.1 … 0.8 for AC 0.8 … 1.
3UG4651 speed monitoring relay 13.7 Technical data 3UG4651-..A.. Field-bound parasitic coupling according to IEC 61000-4-3 Insulation voltage for overvoltage category III according to IEC 60664 with degree of pollution 3 rated value 3UG4651-..W.. 10 V/m V Degree of pollution 300 3 Apparent power consumed • at 24 V for AC maximum V·A 2.
3UG4651 speed monitoring relay 13.7 Technical data Mechanical design 3UG4651-1.... Width mm 22.5 Height mm 86 Depth mm 102 Built in orientation 3UG4651-2....
3UG4651 speed monitoring relay 13.7 Technical data Design of the electrical connection 3UG4651-1.... 3UG4651-2.... screw-type terminals spring-loaded terminals 1x (0.5 ... 4 mm2), 2x (0.5 ... 2.5 mm2) 2x (0.25 ... 1.5 mm2) Type of the connectable conductor cross-section • solid • finely stranded • – with wire end processing 1x (0.5 ... 2.5 mm2), 2x (0.5 ... 1.5 mm2) 2 x (0.25 ... 1.5 mm2) – without wire end processing — 2x (0.25 ... 1.5 mm2) for AWG conductors – solid 2x (20 ...
14 Accessories 14.1 Accessories for 3RR2 current monitoring relays 14.1.1 Sealable cover Description A sealable cover for use with all sizes (3RR2940) is available for the 3RR2 current monitoring relays with digital and analog setting. The sealable cover is used to protect the rotary buttons and the slide switch on the current monitoring relay with analog setting or the buttons on the current monitoring relay with digital setting against unauthorized or unintentional tampering.
Accessories 14.1 Accessories for 3RR2 current monitoring relays 14.1.2 Terminal support for stand-alone assembly Description For a stand-alone assembly or if an overload relay is being used at the same time, adapters for stand-alone installation are available for separate DIN rail mounting or screw mounting. The accessories are exactly the same as the accessories for the 3RU21 thermal overload relay and the 3RB3 solid-state overload relay.
Accessories 14.1 Accessories for 3RR2 current monitoring relays Table 14- 4 Mounting the terminal support (spring-loaded connection system) Step Operating instruction 1 Insert the contacts (a) into the central opening of the main terminals on the terminal support, with the contacts flush to the right. Make sure that the guide tabs are inserted into the designated slots on the terminal support.
Accessories 14.1 Accessories for 3RR2 current monitoring relays Disassembly Table 14- 5 Disassembling the terminal support (screw-type connection system) Step Operating instruction 1 Undo the screws on the main conductor terminals. 2 Release the current monitoring relay by pushing down the clip on the underside of the terminal support. 3 Use a screwdriver to dislodge the terminal support from the current monitoring relay. 4 Pull the current monitoring relay down and away from the contactor.
Accessories 14.2 Accessories for 3UG4 monitoring relays 14.2 Accessories for 3UG4 monitoring relays 14.2.1 Sealable cover Description There is a uniform sealable cover for the monitoring relays with an overall width of 22.5 mm. The sealable cover can be used to secure the actuators (rotary buttons, sliding switches, and keys) of the monitoring relays against unauthorized or unintentional manipulation.
Accessories 14.2 Accessories for 3UG4 monitoring relays 14.2.2 Push-in lugs Description The 3RP1903 push-in lugs are available for the monitoring relays. With the help of the push-in lugs, the monitoring relays can be secured with screws on a level surface (e.g. a wall). Two push-in lugs are required per device. Mounting The figure below shows how to attach the 3RP1903 push-in lugs to the monitoring relay.
Accessories 14.2 Accessories for 3UG4 monitoring relays 14.2.3 Probes for the 3UG4501 monitoring relay 3UG3207-3A three-pole wire electrode The 3UG3207-3A three-pole wire electrode can be used for two-point filling level controls in an insulating tank. In addition to the common reference electrode there is one electrode for the min. value and one for the max. value. The three-pole wire electrode has a length of 500 mm.
Accessories 14.2 Accessories for 3UG4 monitoring relays Note The wire electrode can be cut to the required length or bent before or after installation. The Teflon insulation must be stripped back about 5 mm. 3UG3207-2B two-pole bow electrode Because of the small space requirement on side installation, the 3UG3207-2B two-pole bow electrode for leakage monitoring and level monitoring can be used in small vessels and tubes. The probe can also be used to warn of the ingress of water into a casing. 0.
Accessories 14.
Accessories 14.2 Accessories for 3UG4 monitoring relays 14.2.4 Summation current transformer for the 3UG4624 monitoring relay Description The 3UL22 summation current transformers acquire residual current in machines and plants. Together with the 3UG4624 residual current monitoring relay or the motor management and control unit SIMOCODE 3UF, residual current monitoring and ground-fault monitoring are possible.
Accessories 14.2 Accessories for 3UG4 monitoring relays Technical data Table 14- 10 Technical data - 3UL22 summation current transformer Order number 3UL2201 Rated insulating voltage Ui (50/60 Hz) V AC 690 Rated residual current IΔn without a response delay A 0,3 ... 1 Permissible ambient temperature °C -20 ... +70 Feed-through opening mm For Protodur cable push-through 14.2.5 max. mm2 3UL2202 3UL2203 1000 0,3 ... 40 0,3 ...
Accessories 14.2 Accessories for 3UG4 monitoring relays ① ② ③ ④ Suitable FI type Circuit Load current Fault current Figure 14-7 Possible fault current forms and suitable residual current devices More information is available on the Internet (www.siemens.com/industrial-controls/support).
Accessories 14.2 Accessories for 3UG4 monitoring relays 14.2.5.2 Installation specifications Note Please ensure strict adherence to the installation specifications for live cables. WARNING Open-circuit voltage may result in death, serious injury or material damage The current transformer output is a constant current power supply. In accordance with U = R * I, the output voltage increases with an increasing resistance.
Accessories 14.2 Accessories for 3UG4 monitoring relays All live cables must be routed as close to the center of the transformer as possible. Any neutral conductor must be routed through the transformer. Grounded protective conductors must not be routed through the transformer or need to be routed through the transformer in both directions.
Accessories 14.2 Accessories for 3UG4 monitoring relays The internal transformer diameter must be at minimum twice the size of the power cable bundle diameter.
Accessories 14.2 Accessories for 3UG4 monitoring relays Transformer connection Transformer connecting cables must be twisted and not routed in parallel to live cables to protect from emitted interference. Keep the length of the connecting cables to a minimum. The resistance at the transformer connecting cable must not exceed 5 Ω to ensure correct fault current monitoring. This is ensured by the following limits given here as examples. Conductor cross-section [mm²] AWG/[kcmil] Max. cable length [m] 0.
Accessories 14.2 Accessories for 3UG4 monitoring relays 14.2.5.3 Potential for optimization Potential for optimization in the event of extremely high currents, false tripping due to high starting currents or in environments with high EMC interference 1. Extend the ON-delay time to fade out fault currents measured during motor startup. 2. Extend the tripping delay time to prevent false tripping due to EMC interference. 3. Select a residual current transformer with a larger internal diameter.
Accessories 14.2 Accessories for 3UG4 monitoring relays b) A solid shield sleeve, e.g. turned from a normal, low-carbon tool steel must be precisely in contact with the internal ring of the residual current transformer. The wall thickness of the sleeve must be 1 mm at minimum, the length of the sleeve (L) must correspond to the internal diameter of the transformer used. / ① ② ③ 14.2.5.
Accessories 14.2 Accessories for 3UG4 monitoring relays Parallel connections of conductors If several residual current monitoring relays are installed in one network, a conductor routed through several residual current transformers must not be connected to itself downstream of the transformer, as this would effectively represent a parallel connection of the conductor. This fault occurs particularly often with neutral conductors. This fault causes the currents to be distributed across the conductor.
Accessories 14.2 Accessories for 3UG4 monitoring relays Mixing up conductors In a network with several loads there is the risk that active conductors of loads that are to be separately monitored for fault currents can get mixed up. This fault leads to false tripping as the inflowing and outflowing currents are not always exactly the same strength, even if the loads are identical.
Accessories 14.2 Accessories for 3UG4 monitoring relays Routing contrary to the current flow To be able to form the vectorial sum of currents to and from a load correctly, all active conductors must be routed through the residual current transformer from the same direction. Due to the restricted space in a control cabinet it may be easier to route the neutral conductor through the transformer in the opposite direction to the phase conductor.
Accessories 14.2 Accessories for 3UG4 monitoring relays 14.2.5.6 Installing Wall mounting procedure Step Instructions 1/2 Insert the fixing lugs into the designated openings in the unit until they reach the stop. 3 Place the device against the wall surface prepared for establishing a screw connection. 4 Insert the head screws through the corresponding elongated holes in the fixing lugs. 5 Screw the device onto the level surface so that it is secure.
Accessories 14.2 Accessories for 3UG4 monitoring relays Rail mounting Requirement: At the installation location, a horizontal 35-mm wide mounting rail in accordance with DIN EN 60715 has been properly secured. Rail mounting is possible with residual current transformers with bushing opening diameters of up to ∅ 55 mm only (3UL2302-1A, 3UL2303-1A). Step Instructions 1 Mount the holder (3UL2900) to the device. 2 Mount the device to the rail.
Accessories 14.2 Accessories for 3UG4 monitoring relays 14.2.5.7 Technical data 3UL2302/3UL2303/3UL2304 residual current transformers for fault current monitoring 3UL2302-1A Product equipment touch-protection 3UL2303-1A 3UL2304-1A Yes Height mm 64 Width mm 70 92 124.5 Depth mm 75.5 98 130 °C -25 … +60 55 80 Ambient temperature • during operating screw fixing Type of mounting Diameter of the feedthrough mm Conductor cross section that can be mm² connected of the terminal 35 2.
Accessories 14.2 Accessories for 3UG4 monitoring relays 3UL2305/3UL2306/3UL2307 residual current transformers for fault current monitoring 3UL2305-1A Product equipment touch-protection 3UL2306-1A 3UL2307-1A Yes Height mm 64 62 Width mm 163 201 300 Depth mm 169 207.5 286 °C -25 … +60 140 210 Ambient temperature • during operating screw fixing Type of mounting Diameter of the feedthrough mm Conductor cross section that can be mm² connected of the terminal 110 2.
Accessories 14.2 Accessories for 3UG4 monitoring relays 14.2.5.8 Dimension drawings 3UL23 residual current transformer 70 5 50 64 6.2 75.
Accessories 14.2 Accessories for 3UG4 monitoring relays 92 5 98 ෘ5 6.2 50 64 38 Figure 14-10 3UL2303-1A 124.5 0 130 ෘ8 50 64 6.
Accessories 14.2 Accessories for 3UG4 monitoring relays 163 169 10 ෘ1 64 50 6.2 84.5 Figure 14-12 3UL2305-1A 201 40 64 50 110 6.2 207.
Accessories 14.2 Accessories for 3UG4 monitoring relays 300 10 62 46 161 6.
Accessories 14.3 Accessories for 3UG458. insulation monitoring relays. 14.3 Accessories for 3UG458. insulation monitoring relays. 14.3.1 Sealable cover Description A sealable cover compatible is available for the 3UG458. insulation monitoring relays.
Accessories 14.3 Accessories for 3UG458. insulation monitoring relays. 14.3.2 3UG4983 upstream module for the 3UG4583 monitoring relay Description The 3UG4983-1A passive upstream module is used for extending the measuring range of the 3UG4583 insulation monitoring relays. The upstream module enables monitoring of the insulation resistance in systems with rated system voltages of up to 690 V AC (15 to 400 Hz) and 1000 V DC in accordance with IEC 61557-8.
Accessories 14.3 Accessories for 3UG458. insulation monitoring relays. Mounting onto standard rail The figure below shows how to install the 3UG4983 upstream module on a standard rail. Table 14- 13 Installing the 3UG4983 upstream module (mounting onto standard rail) Step Instructions 1/2 Position the device on the top edge of the mounting rail and press it down until it snaps onto the bottom edge of the rail.
Accessories 14.3 Accessories for 3UG458. insulation monitoring relays. 14.3.2.1 Internal circuit diagrams Internal circuit diagram 3UG983-1A 3UG4983-1A .
Accessories 14.3 Accessories for 3UG458. insulation monitoring relays. Wiring examples for the 3UG4583 insulation monitoring relay with connected 3UG4983 upstream module Measuring inputs L+ and L- can be connected to any conductor. Measuring inputs L+ and Lmust always be connected to different conductors. The rated system voltage is Un ≤ 690 V AC (15 to 400 Hz) or Un ≤ 1000 V DC.
Accessories 14.3 Accessories for 3UG458. insulation monitoring relays. Application example The figure below shows how to connect the 3UG4983 upstream module to the 3UG4583 insulation monitoring relay. / / / 1 3( 9/ $ < < < 8* $ 8* &: 9/ / 9 / 9 96 9( 9 / 96 9 9 / .
Accessories 14.3 Accessories for 3UG458. insulation monitoring relays. 14.3.2.
Accessories 14.3 Accessories for 3UG458. insulation monitoring relays.
Accessories 14.3 Accessories for 3UG458. insulation monitoring relays.
A References Further references You will find further information on the 3RR2 and 3UG4 monitoring relays on the Internet (http://support.automation.siemens.com/WW/view/en/20356134/133300). In addition to this manual, please refer to the operating instructions and manuals for any accessories. You can download the relevant documentation from the Internet (www.siemens.de/automation/csi/manual). Simply enter the order number of the relevant item into the search field.
References Title Order number SIRIUS monitoring relay for power factor and active current monitoring 3ZX1012-0UG46-4BA1 (3UG4641) SIRIUS monitoring relay for speed monitoring (3UG4651) 3ZX1012-0UG46-5BA1 Title Reference Functional safety - Use of SIRIUS 3UG4 and 3RR2 monitoring relays with integrated sensors Internet (http://support.automation.si emens.
Parameters B Nominal line voltage The nominal voltage is the value of the electrical voltage during normal operation specified by the manufacturer. The nominal voltage is usually stated with a maximum permissible tolerance range. In Europe, the nominal value of the line voltage, the nominal line voltage, is 230 V (line / neutral) or 400 V (line / line).
Parameters Tripping delay time If the measured value overshoots or undershoots the set limit value, the delay time that can be set using the "Tripping delay time" parameter starts. On expiry of this time, the switching contact changes state and a message may be sent via IO-Link.
Parameters Starting the ON-delay time via IO-Link The ON-delay time can also be started through the process image of the outputs (PIQ) by setting the control command "Start ON delay time." This is a simple method of permitting brief load steps during operation if these are predictable. The ON-delay time can be set either locally via the three keys on the device, or via IO-Link.
Parameters (Warning) threshold for undershoot The device monitors a measured value for undershoot. The measured value can be parameterized as a threshold or as a warning threshold (on the 3RR22 and 3UG4583 devices only) for undershoot. The warning threshold defines the switching threshold of the relevant output relay prior to tripping by measured value undershoot.
Parameters Possible indications on the display: ● Current overshoot: I▲ (threshold), I!▲ (warning threshold) ● Voltage overshoot: U▲ (threshold), possibly U!▲ (warning threshold) ● Speed overshoot: rpm▲ (threshold), possibly rpm!▲ (warning threshold) ● Power factor overshoot: φ▲ (threshold), possibly φ!▲ (warning threshold) ● Active current overshoot: Ir▲ (threshold), possibly Ir!▲ (warning threshold) ● Fault current overshoot: I▲(threshold), possibly I! (warning threshold) Reset response The setting of t
Parameters Hysteresis Hysteresis is the continuation of an effect within the hysteresis range after its cause has been removed; its purpose is to prevent repeated response in the threshold value range. &RUUHFW UDQJH 1RUPDO UDQJH 7KUHVKROG IRU RYHUVKRRW +\VW 7KUHVKROG IRU XQGHUVKRRW +\VW Figure B-1 0HDVXUHG YDOXH +\VWHUHVLV WKUHVKROG IRU WKH WKUHVKROG IRU RYHUVKRRW +\VWHUHVLV WKUHVKROG IRU WKH WKUHVKROG IRU XQGHUVKRRW Explanation of hysteresis If, after the upper threshold value has been ov
Parameters Fault current monitoring If fault current monitoring has been activated (I >> = yes) and the total current of the load currents at terminals 1L1 / 2T1, 3L2 / 4T2 and 5L3 / 6T3 rises above the permissible threshold (S00: 1.5 A / S0: 4 A), the ON-delay time onDel, the tripping delay time Del, and the restart delay time RsDel are stopped and both the CO contact and the semiconductor output change their switching state immediately (≤ 200 ms).
Parameters Current monitoring principle The monitoring relays monitor an AC load current which flows through the device terminals depending on whether monitoring has been set to check for overshoot or undershoot, or window monitoring.
Parameters Relay switching behavior An output relay responds in accordance with the set switching behavior. Several variations can be distinguished here: ● Closed-circuit principle (NC) If the closed-circuit principle is selected, the output relay picks up when the voltage is applied (contact .1/.4 closed). The output relay drops out in the event of a fault (contact .1/.2 closed).
Parameters Sensor sensitivity The sensor sensitivity is the sensitivity R sens, with which the filling level monitoring relay must respond. The working principle of the filling level monitoring relays is based on resistance measurement of conductive liquids (conductive measurement method). This method can be used with all liquids and substances that have a resistivity < 200 kΩ.
Parameters Stabilization delay An output is only switched to the "correct position" after switching on the supply voltage if all monitored measured values are stable for the duration of the stabilization delay. The monitoring functions are active within the stabilization delay. A threshold overshoot or undershoot in this time does not result in a fault, but instead in restarting of the stabilization delay.
Parameters 3UG4 / 3RR2 monitoring relays 362 Manual, 02/2013, NEB927043002000/RS-AA/002
C Dimension Drawings C.1 Dimension drawings 3RR2 monitoring relay 3RR2.41-1A.30 (screw connection, S00) 33RR2.41-1A.30 with terminal support for stand-alone assembly 3RR2.41-1A.30 with contactor 3RR2.41-2A.30 (spring-loaded connection, S00) 3RR2.41-2A.30 with terminal support for stand-alone assembly 3RR2.41-2A.
Dimension Drawings C.1 Dimension drawings 3RR2 monitoring relay 3RR2.42-1A.30 (screw connection, S0) D 3RR2.42-1A.30 with terminal support for stand-alone assembly 3RR2.42-1A.30 with contactor 3RR2.42-2A.30 (spring-loaded connection, S0) 3RR2.42-2A.30 with terminal support for stand-alone assembly 3RR2.42-2A.
Dimension Drawings C.2 Dimension drawings 3UG4 monitoring relays C.2 Dimension drawings 3UG4 monitoring relays C.2.1 Dimension drawings 3UG4 monitoring relays. (2 connecting terminals) 3UG4. monitoring relays with 2 connecting terminals (screw-type connection) 6,5,86 Figure C-1 3UG4. monitoring relays with 2 connecting terminals with screw-type connections 3UG4.
Dimension Drawings C.2 Dimension drawings 3UG4 monitoring relays C.2.2 Dimension drawings 3UG4 monitoring relays. (3 connecting terminals) 3UG4. monitoring relays with 3 connecting terminals (screw-type connection) 6,5,86 Figure C-3 3UG4. monitoring relays with 3 connecting terminals with screw-type connections 3UG4.
Dimension Drawings C.2 Dimension drawings 3UG4 monitoring relays C.2.3 Dimension drawings 3UG4 monitoring relays. (4 connecting terminals) 3UG4. monitoring relays with 4 connecting terminals (screw-type connection) 6,5,86 Figure C-5 3UG4.
Dimension Drawings C.2 Dimension drawings 3UG4 monitoring relays 3UG4. monitoring relays with 4 connecting terminals (spring-loaded connections) 6,5,86 Figure C-6 3UG4.
Dimension Drawings C.2 Dimension drawings 3UG4 monitoring relays C.2.4 Dimension drawings 3UG458 insulation monitoring relay.
Dimension Drawings C.
D Menu-based operation 3UG4614 line monitoring relay Run 1) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 2) >500m s V a lu e 1) 1) 1) 1) 1) 1) >500m s >2s Set >2s E rro r >2s >2s + >500m s >500m s + no 1) ye s M e m o ry ? 1) 1) 2) On D el O ff 11 21 12 14 22 24 Upper limit value ... overshot ... not overshot Lower limit value ... not undershot ...
Menu-based operation 3UG4615 line monitoring relay Run ! PV Value ! PV ! V Set ! V Error ! V ! V ! PV ! PV QR 1) 2Q 'HO 2II 2) \HV 0HPRU\ " 8SSHU OLPLW YDOXH RYHUVKRW QRW RYHUVKRW /RZHU OLPLW YDOXH QRW XQGHUVKRW XQGHUVKRW 3UG4 / 3RR2 monitoring relays 372 Manual, 02/2013, NEB927043002000/RS-AA/002
Menu-based operation 3UG4616 line monitoring relay Run 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) >500ms Value 1) 1) 1) 1) 1) 1) >500ms >2s Set >2s Error >2s + >2s + >500ms >500ms no 1) yes 1) On Del Off 1) 11 12 14 2) Memory ? 21 22 24 Upper limit value ... overshot ... not overshot Lower limit value ... not undershot ...
Menu-based operation 3UG4617 line monitoring relay Run 2) 1) 1) 2) 1) 2) 1) 2) 1) 2) 1) 2) >500ms Value 1) 1) 1) 1) 1) 1) 1) 1) 1) >500ms >2s Set >2s Error >2s + >2s >500ms + no >500ms 1) 1) On Del Off 1) 11 1214 2) yes Memory ? 21 22 24 Upper limit value ... overshot ... not overshot Lower limit value ... not undershot ...
Menu-based operation 3UG4618 line monitoring relay Run 2) 1) 1) 1) 2) 2) 1) 2) 1) 2) 1) 2) >500ms Value 1) 1) 1) 1) 1) 1) 1) 1) 1) >500ms >2s Set >2s Error >2s + >2s >500ms + no >500ms 1) 1) 2) yes Memory ? 1) On Del Off 11 21 12 14 22 24 Upper limit value ... exceeded ... not exceeded Lower limit value ... not undershot ...
Menu-based operation 3UG4621 current monitoring relays Run Example 1) 2) >500ms Value 1) 1) 1) 1) 1) 1) 1) 1) >500ms >2s >2s Set Error >2s + >2s >500ms + yes >500ms no 1) 2) 1) Memory? 1) 2) On 11 Del 2) 2) 12 14 Off 2) Depending on the setting in menu " Value" Display Upper limit value exceeded not overshot Display Lower limit value Not Fallen below Fallen below Display Limit exceeded not overshot/undershot Fallen below 3UG4 / 3RR2 monitoring relays 376 Manual, 02
Menu-based operation 3UG4622 current monitoring relays Run Example 1) 2) >500ms Value 1) 1) 1) 1) 1) 1) 1) 1) >500ms >2s >2s Set Error >2s + >2s >500ms >500ms + yes no 1) 1) 2) 2) 1) Memory? On 11 Del 2) 2) Off 12 14 2) Depending on the setting in menu " Value" Display Upper limit value exceeded Not exceeded Display Lower limit value Not Fallen below Fallen below Display Limit exceeded not overshot/undershot Fallen below 3UG4 / 3RR2 monitoring relays Manual, 02/201
Menu-based operation 3UG4624 residual current monitoring relay Run 1) 2) >500ms Value 3) 1) 1) 1) 1) 1) 1) 1) >500ms >2s >2s Set >2s Error >500ms 3) + >2s + >500ms yes 1) 3) no Memory ? 3) 1) 11 On Del 12 14 Off 21 On Off 22 24 2) Display upper limit value and warning threshold not overshot Display Only warning threshold overshot Display Upper limit overshot 3UG4 / 3RR2 monitoring relays 378 Manual, 02/2013, NEB927043002000/RS-AA/002
Menu-based operation 3UG4625 residual current monitoring relay 1) Run On 11 Del/OnDel 1) 2) 12 14 Off 21 On OnDel >500ms 22 24 Off Value 2) 1) 1) Threshold and warning threshold ...exceeded ...
Menu-based operation 3UG4631 voltage monitoring relay Run 2) 1) >500ms Value 1) 1) 1) 1) 1) 1) 1) 1) >500ms >2s >2s Set Error >2s + >2s >500ms >500ms + yes no Memory ? 1) 1) 2) 2) 2) 2) 1) On 11 Del 12 14 Off 2) Depending on the setting in menu " Value" Display Upper limit value exceeded not overshot Display Lower limit value Not Fallen below Fallen below Display Limit exceeded not overshot/undershot Fallen below 3UG4 / 3RR2 monitoring relays 380 Manual, 02/2013, NE
Menu-based operation 3UG4632 voltage monitoring relay Run 2) 1) >500ms Value 1) 1) 1) 1) 1) 1) 1) 1) >500ms >2s >2s Set Error >2s + >2s >500ms + no >500ms 1) 1) 2) 2) 2) 1) yes Memory? 2) On 11 Del 12 14 Off 2) Depending on the setting in menu " Value" Display Upper limit value exceeded not overshot Display Lower limit value Not Fallen below Fallen below Display Limit exceeded not overshot/undershot Fallen below 3UG4 / 3RR2 monitoring relays Manual, 02/2013, NEB9270430
Menu-based operation 3UG4633 voltage monitoring relay Run 2) 1) >500ms Value 1) 1) 1) 1) 1) 1) 1) 1) >500ms >2s >2s Set Error >2s + >2s >500ms >500ms + no 1) 1) 2) 2) 1) yes Memory ? On 11 Del 12 14 2) 2) Off 2) Depending on the setting in menu " Value" Display Upper limit value exceeded not overshot Display Lower limit value Not Fallen below Fallen below Display Limit exceeded not overshot/undershot Fallen below 3UG4 / 3RR2 monitoring relays 382 Manual, 02/2013, NEB9
Menu-based operation 3UG4641 cos phi and active current monitoring relay Run 1) 2) 1) 2) 1) 2) 2) 1) >500ms Value 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) 1) >500ms >2s >2s Set Error >2s + >2s >500ms >500ms yes no 1) 1) 2) 1) 2) 1) 2) 11 21 12 14 22 24 + Memory ? On Del 2) Off Depending on the setting in menu " Value" Display upper limit value (21-22-24) exceeded not overshot Display lower limit value (11-12-14) not undershot Fallen below Display
Menu-based operation 3UG4651 speed monitoring relay Run 1) 1) 2) 2) > 500ms Value 1) 1) 1) 1) 1) 1) 1) 1) > 500ms >2s Set >2s Error + >2s >2s >2s yes > 500ms no > 500ms + >500ms Memory? 1) 2) 1) 2) 1) 11 On Del Off 12 14 2)Depending on the setting in menu " Value" Display Upper limit value exceeded not overshot Display Lower limit value not undershot Display Limit exceeded not overshot/undershot Fallen below Fallen below 3UG4 / 3RR2 monitoring relays 384 Manual,
E Correction sheet Correction sheet Have you noticed any errors while reading this manual? If so, please use this form to tell us about them. We welcome comments and suggestions for improvement.
Correction sheet 3UG4 / 3RR2 monitoring relays 386 Manual, 02/2013, NEB927043002000/RS-AA/002
Index 2 2-wire AC system 3UG4581-1AW30, 217 3UG4582-1AW30, 244 3UG4583-1CW30, 246 3UG4583-1CW30 and 3UG4983-1A, 344 2-wire DC system 3UG4582-1AW30, 244 3UG4583-1CW30, 246 3UG4583-1CW30 and 3UG4983-1A, 344 3 3UG4983 upstream module, 231 3-wire AC system 3UG4581-1AW30, 217 3UG4582-1AW30, 244 3UG4583-1CW30, 246 3UG4583-1CW30 and 3UG4983-1A, 344 3-wire DC system 3UG4582-1AW30, 244 3UG4583-1CW30, 246 3UG4583-1CW30 and 3UG4983-1A, 344 4 4-wire AC system 3UG4581-1AW30, 217 3UG4582-1AW30, 244 3UG4583-1CW30, 246
Index 3UG4512 line monitoring relay, 101 3UG4513 line monitoring relay, 111 3UG4581 insulation monitoring relay, 215 3UG4582/3UG4583 insulation monitoring relays, 242 3UG4614 line monitoring relay, 122 3UG4615 / 3UG4616 line monitoring relays, 134 3UG4617 / 3UG4618 line monitoring relays, 146 3UG4621/3UG4622 current monitoring relays, 160 3UG4624 residual current monitoring relay, 179 3UG4625 residual current monitoring relay, 197 3UG4631/3UG4632/3UG4633 voltage monitoring relay, 267 3UG4641 cos phi and ac
Index M 3UG4582/3UG4583 insulation monitoring relays, 238 Manual RESET, 355 3UG4614 line monitoring relay, 121 Manuals, 350 3UG4615 / 3UG4616 line monitoring relays, 133 Memory function, 230 3UG4617 / 3UG4618 line monitoring relays, 145 Menu navigation, 39 3UG4621/3UG4622 current monitoring relays, 159 Menu-based operation, 36 3UG4624 residual current monitoring relay, 177 Minimum clearance 3UG4625 residual current monitoring relay, 196 3RR2 current monitoring relays, 26 3UG463.
Index 3RR2 current monitoring relays, 311 Sensor sensitivity, 360 Setting, 36 Snap-on mounting 3UG4 monitoring relay, 31 3UG458. monitoring relay.
Service & Support Download catalogs and information material: www.siemens.com/sirius/infomaterial Newsletter - always up to date: www.siemens.com/sirius/newsletter E-Business in the Industry Mall: www.siemens.com/sirius/mall Online-Support: www.siemens.com/sirius/support Contact for all technical information: Technical Assistance Tel.: +49 (911) 895-5900 e-mail: technical-assistance@siemens.com www.siemens.com/sirius/technical-assistance Siemens AG Industry Sector Postfach 23 55 90713 FUERTH GERMANY www.