Data Sheet

Data sheet 3VA1112-3ED26-0AA0
CIRCUIT BREAKER 3VA1 IEC FRAME 160 BREAKING CAPACITY
CLASS N ICU=25KA @ 415 V 2-POLE, LINE PROTECTION
TM210, FTFM, IN=125A OVERLOAD PROTECTION IR=125A
FIXED SHORT CIRCUIT PROTECTION II=10 X IN CABLE
CONNECTION
Model
product brandname SENTRON
Product designation Molded case circuit breaker
Design of the product Line protection
Type of load switch / according to UL 489 / Heating,
Air Conditioning, and Refrigeration circuit breaker
(HACR Type)
Yes
Design of the overcurrent release TM210
Protective function of the overcurrent release LI
Number of poles 2
General technical data
Tension assignée d'isolement Ui 500V
Max. rated operational voltage Ue with AC 50/60Hz 415V
Max. rated operational voltage Ue with DC 250V
Active power loss / for rated value of the current / at
AC / in hot operating state / per device
15.5W
Active power loss / for rated value of the current / at
AC / in hot operating state / per pole
7.75W
Mechanical service life (switching cycles) / typical 15000
3VA1112-3ED26-0AA0 Subject to change without notice
Page 1/
5
11/21/2016 © Copyright Siemens AG