Datasheet
Data sheet 3VA1116-3ED36-0AA0
circuit breaker 3VA1 IEC frame 160 breaking capacity class N
Icu=25kA @ 415V 3-pole, line protection TM210, FTFM, In=160A
overload protection Ir=160A fixed short-circuit protection Ii=10 x In
clamp connection
Model
Product brand name SENTRON
Product designation Molded case circuit breaker
Product version Line protection
Design of the overcurrent release TM210
Protective function of the overcurrent release LI
Number of poles 3
General technical data
Rated insulation voltage Ui 800V
Max. rated operational voltage Ue with AC 50/60Hz 690V
Max. rated operational voltage Ue with DC 500V
Power loss [W] / maximum 38W
Active power loss / for rated value of the current / at
AC / in hot operating state / per pole
12.67W
Latching - endurance 20000
Electrical endurance (switching cycles) / at AC-1 / at
380/415 V 50/60 Hz
8000
Electrical endurance (switching cycles) / at AC-1 / at
690 V 50/60 Hz
8000
3VA1116-3ED36-0AA0 Subject to change without notice
Page 1/
7
01/30/2019 © Copyright Siemens