Data Sheet

Neutral conductors / upgradeable/retrofittable No
Ground fault monitoring version Without
Product function
● communication function
No
● other measurement function
No
Net weight 1.2kg
Current
Max. rated operational current of the frame size 160A
Rated continuous current Iu 160A
Operating current
● at 40 °C
160A
● at 45 °C
160A
● at 50 °C
160A
● at 55 °C
158A
● at 60 °C
155A
● at 65 °C
153A
● at 70 °C
150A
Switching capacity according to IEC 60947
Switching capacity class of the circuit breaker M
Maximum short-circuit current breaking capacity (Icu)
● at 240 V
85kA
● at 415 V
55kA
● at 440 V
36kA
● at 500 V
10kA
● at 690 V
10kA
Operational short-circuit current breaking capacity
(Ics)
● at 240 V
85kA
● at 415 V
55kA
● at 440 V
36kA
● at 500 V
5kA
● at 690 V
5kA
Short-circuit current making capacity (Icm)
● at 240 V
187kA
● at 415 V
121kA
● at 440 V
76kA
● at 500 V
17kA
● at 690 V
17kA
Design of short-circuit protection For switching power values in DC networks, see the 3VA molded
case circuit breaker device manual; link to be found under Service
& Support in the last chapter
3VA1116-5FF46-0AA0 Subject to change without notice
Page 2/
7
07/15/2019 © Copyright Siemens