Datasheet

Data sheet 3VA1132-3ED16-0AA0
circuit breaker 3VA1 IEC frame 160 breaking capacity class N
Icu=25kA @ 240V 1-pole, line protection TM210, FTFM, In=32A
overload protection Ir=32A fixed short-circuit protection Ii=10 x In
clamp connection
Model
Product brand name SENTRON
Product designation Molded case circuit breaker
Product version Line protection
Design of the overcurrent release TM210
Protective function of the overcurrent release LI
Number of poles 1
General technical data
Rated insulation voltage Ui 500V
Max. rated operational voltage Ue with AC 50/60Hz 415V
Max. rated operational voltage Ue with DC 125V
Power loss [W] / maximum 3.5W
Active power loss / for rated value of the current / at
AC / in hot operating state / per pole
3.5W
Latching - endurance 20000
Electrical endurance (switching cycles) / at AC-1 / at
380/415 V 50/60 Hz
8000
Electrical endurance (switching cycles) / at AC-1 / at
690 V 50/60 Hz
8000
3VA1132-3ED16-0AA0 Subject to change without notice