Datasheet

Neutral conductors / upgradeable/retrofittable No
Ground fault monitoring version Without
Product function
● communication function
No
● other measurement function
No
Net weight 1.026kg
Electricity
Max. rated operational voltage of the size of the
circuit-breaker
160A
Rated continuous current Iu 32A
Operating current
● at 40 °C
32A
● at 45 °C
32A
● at 50 °C
32A
● at 55 °C
31.04A
● at 60 °C
31A
● at 65 °C
30A
● at 70 °C
30A
Switching capacity according to IEC 60947
Switching capacity class of the circuit breaker N
Maximum short-circuit current breaking capacity (Icu)
● at 240 V
36kA
● at 415 V
25kA
● at 440 V
16kA
● at 500 V
7kA
● at 690 V
7kA
Operational short-circuit current breaking capacity
(Ics)
● at 240 V
36kA
● at 415 V
25kA
● at 440 V
16kA
● at 500 V
5kA
● at 690 V
5kA
Short-circuit current making capacity (Icm)
● at 240 V
76kA
● at 415 V
53kA
● at 440 V
32kA
● at 500 V
11.9kA
● at 690 V
11.9kA
Adjustable parameters
Adjustable response value current / lr min. 22A
3VA1132-3EE36-0AA0 Subject to change without notice