Data Sheet

Electrical endurance (switching cycles) / at AC-1 / at
380/415 V 50/60 Hz
8000
Neutral conductors / upgradeable/retrofittable No
Ground fault monitoring version Without
Product function
● communication function
No
● other measurement function
No
Net weight 1.026kg
Electricity
Marking / according to UL 489 / 100%-rated breaker No
Max. rated operational voltage of the size of the
circuit-breaker
160A
Courant permanent assigné Iu 40A
Operating current
● at 40 °C
40A
● at 45 °C
40A
● at 50 °C
40A
● at 55 °C
39A
● at 60 °C
39A
● at 65 °C
38A
● at 70 °C
37A
Switching capacity according to IEC 60947
Switching capacity class of the circuit breaker S
Maximum short-circuit current breaking capacity (Icu)
● at 240 V
55kA
● at 415 V
36kA
● at 440 V
25kA
● at 500 V
16kA
● at 690 V
7kA
Operational short-circuit current breaking capacity
(Ics)
● at 240 V
55kA
● at 415 V
36kA
● at 440 V
25kA
● at 500 V
15kA
● at 690 V
5kA
Short-circuit current making capacity (Icm)
● at 240 V
121kA
● at 415 V
76kA
● at 440 V
53kA
● at 500 V
32kA
● at 690 V
11.9kA