Data Sheet

Product function
● communication function
No
● Phase failure detection
Yes
● other measurement function
No
Net weight 2.4kg
Current
Max. rated operational current of the frame size 250A
Rated continuous current Iu 200A
Operating current
● at 40 °C
200A
● at 45 °C
200A
● at 50 °C
200A
● at 55 °C
192A
● at 60 °C
188A
● at 65 °C
184A
● at 70 °C
180A
Switching capacity according to IEC 60947
Switching capacity class of the circuit breaker M
Maximum short-circuit current breaking capacity (Icu)
● at 240 V
85kA
● at 415 V
55kA
● at 440 V
55kA
● at 500 V
36kA
● at 690 V
10kA
Operational short-circuit current breaking capacity
(Ics)
● at 240 V
85kA
● at 415 V
55kA
● at 440 V
55kA
● at 500 V
36kA
● at 690 V
10kA
Short-circuit current making capacity (Icm)
● at 240 V
187kA
● at 415 V
121kA
● at 440 V
121kA
● at 500 V
75.6kA
● at 690 V
17kA
Adjustable parameters
Adjustable response value current / lr min. 80A
Adjustable response value current / Ir max. 200A
Adjustable response value time / tr min. 4
3VA2220-5MN32-0DA0 Subject to change without notice
Page 2/
6
09/13/2019 © Copyright Siemens