Data Sheet

● communication function
No
● Phase failure detection
No
● other measurement function
No
Net weight 2.6kg
Current
Max. rated operational current of the frame size 250A
Rated continuous current Iu 250A
Operating current
● at 40 °C
250A
● at 45 °C
250A
● at 50 °C
250A
● at 55 °C
241A
● at 60 °C
232A
● at 65 °C
222A
● at 70 °C
213A
Switching capacity according to IEC 60947
Switching capacity class of the circuit breaker L
Maximum short-circuit current breaking capacity (Icu)
● at 240 V
200kA
● at 415 V
150kA
● at 440 V
150kA
● at 500 V
110kA
● at 690 V
24kA
Operational short-circuit current breaking capacity
(Ics)
● at 240 V
200kA
● at 415 V
150kA
● at 440 V
150kA
● at 500 V
110kA
● at 690 V
12kA
Short-circuit current making capacity (Icm)
● at 240 V
440kA
● at 415 V
330kA
● at 440 V
330kA
● at 500 V
242kA
● at 690 V
50.4kA
Adjustable parameters
Adjustable response value current / lr min. 100A
Adjustable response value current / Ir max. 250A
Adjustable response value time / tr min. 0.5
Adjustable response value time / tr max. 15
3VA2225-8HL32-0BH0 Subject to change without notice