Data Sheet

Data sheet 3VA2340-6JQ32-0JH0
circuit breaker 3VA2 IEC frame 400 breaking capacity class H
Icu=85kA @ 415V 3-pole, line protection ETU560, LSIG, In=400A
overload protection Ir=160A...400A short-circuit protection
Isd=0.6...10 x In, Ii=1.5 x In N conductor protection optionally with
external current transformer, up to 160% gr.-fault prot., can be sw. off
Ig=0.2...1 x In, tg=0.05-0.8s nut keeper kit shunt trip (STL) 110-127V
DC, AC 50/60Hz 2 auxiliary switches HQ 1 trip alarm switch HQ
Model
Product brand name SENTRON
Product designation Molded case circuit breaker
Product version Line protection
Design of the overcurrent release ETU560
Protective function of the overcurrent release LSIG
Number of poles 3
Design of the auxiliary release Shunt trip (STL)
Auxiliary contact version 2 auxiliary switches + 1 trip alarm switch HQ
General technical data
Rated insulation voltage Ui 800V
Max. rated operational voltage Ue with AC 50/60Hz 690V
Power loss [W] / maximum 96W
Active power loss / for rated value of the current / at
AC / in hot operating state / per pole
32W
Latching - endurance 15000
Electrical endurance (switching cycles) / at AC-1 / at
380/415 V 50/60 Hz
6000
Neutral conductors / upgradeable/retrofittable Yes
3VA2340-6JQ32-0JH0 Subject to change without notice