Data Sheet

Adjustable response value time / tr min. 0.5
Adjustable response value time / tr max. 17
Adjustable response value current / Isd min. 240A
Adjustable response value current / Isd max. 4000A
Short-term delayed / tripping switchable /
I2t=ON/OFF
Yes
Adjustable response value time / tsd min. 0.05s
Adjustable response value time / tsd max. 0.5s
Adjustable response value current / li min. 600A
Adjustable response value current / li max. 4000A
Ground fault protection can be switched ON/OFF Yes
Adjustable response value current / lg min. 80A
Adjustable response value current / lg max. 400A
Mechanical Design
Height 248mm
Width 138mm
Depth 110mm
Connections
Arrangement of electrical connectors / for main
current circuit
Front terminal
Type of electrical connection / for main current circuit Lug terminal
Type of connectable conductor cross-section,
connection screw, width x thickness , min.
20 x 1
Type of connectable conductor cross-section,
connection screw, width x thickness , max.
35 x 10
Auxiliary circuit
Product component
● undervoltage release
No
● Voltage trigger
Yes
● undervoltage release with leading contact
No
● Trip indicator
Yes
Number of CO contacts / for auxiliary contacts 3
Accessories
Product extension / optional / motor drive Yes
Manufacturer's article number
● of the supplied basic switch
3VA2340-6JQ32-0AA0
● of the integrated auxiliary switch/alarm switch
3VA9988-0AA12
● of the integrated auxiliary switch/alarm switch
3VA9988-0AB12
● of the integrated auxiliary trip
3VA9688-0BL32
Environmental conditions
Protection class IP / on the front IP40
3VA2340-6JQ32-0JH0 Subject to change without notice
Page 3/
6
09/14/2019 © Copyright Siemens