Data Sheet

Ground fault monitoring version Without
Product function
● communication function
No
● other measurement function
No
Net weight 4.3kg
Current
Max. rated operational current of the frame size 500A
Rated continuous current Iu 500A
Short-time current resistance (Icw)
● limited to 0.5 s
6kA
● limited to 1 s
6kA
Operating current
● at 40 °C
500A
● at 45 °C
500A
● at 50 °C
500A
● at 55 °C
495A
● at 60 °C
490A
● at 65 °C
485A
● at 70 °C
480A
Switching capacity according to IEC 60947
Switching capacity class of the circuit breaker C
Maximum short-circuit current breaking capacity (Icu)
● at 240 V
150kA
● at 415 V
110kA
● at 440 V
110kA
● at 500 V
85kA
● at 690 V
6kA
Operational short-circuit current breaking capacity
(Ics)
● at 240 V
150kA
● at 415 V
110kA
● at 440 V
110kA
● at 500 V
85kA
● at 690 V
6kA
Short-circuit current making capacity (Icm)
● at 240 V
330kA
● at 415 V
242kA
● at 440 V
242kA
● at 500 V
187kA
● at 690 V
13kA
Adjustable parameters
3VA2450-7HK32-0AA0 Subject to change without notice
Page 2/
7
09/14/2019 © Copyright Siemens