Data Sheet

Adjustable response value current / lr min. 200A
Adjustable response value current / Ir max. 500A
Adjustable response value time / tr min. 600
Adjustable response value time / tr max. 600
Short-term delayed / tripping switchable /
I2t=ON/OFF
No
Adjustable response value current / li min. 7000A
Adjustable response value current / li max. 7000A
Ground fault protection / tripping switchable /
I2t=ON/OFF
No
Mechanical Design
Height [in] 9.8in
Height 248mm
Width [in] 5.4in
Width 138mm
Depth [in] 4.3in
Depth 110mm
Connections
Arrangement of electrical connectors / for main
current circuit
Front terminal
Type of electrical connection / for main current circuit Lug terminal
Type of connectable conductor cross-section,
connection screw, width x thickness , min.
20 x 1
Type of connectable conductor cross-section,
connection screw, width x thickness , max.
35 x 10
Auxiliary circuit
Number of CO contacts / for auxiliary contacts 0
Accessories
Product extension / optional / motor drive Yes
Environmental conditions
Protection class IP / on the front IP40
Ambient temperature
● during operation / minimum
-25°C
● during operation / maximum
70°C
● during storage / minimum
-40°C
● during storage / maximum
80°C
Certificates
Reference code / acc. to DIN EN 81346-2 Q
3VA2450-7HK32-0AA0 Subject to change without notice
Page 3/
7
09/14/2019 © Copyright Siemens