Data Sheet

Data sheet 3VA2463-6JP32-0AD0
circuit breaker 3VA2 IEC frame 630 breaking capacity class H
Icu=85kA @ 415V 3-pole, line protection ETU550, LSI, In=630A
overload protection Ir=250A...630A short-circuit protection Isd=0.6..9
x In, Ii=1.5..9 x In N conductor protection optionally with external
current transformer, up to 160% nut keeper kit 3 auxiliary switches
HQ
Model
Product brand name SENTRON
Product designation Molded case circuit breaker
Product version Line protection
Design of the overcurrent release ETU550
Protective function of the overcurrent release LSI
Number of poles 3
Design of the auxiliary release Without auxiliary release
Auxiliary contact version 3 auxiliary switches HQ
General technical data
Rated insulation voltage Ui 800V
Max. rated operational voltage Ue with AC 50/60Hz 690V
Power loss [W] / maximum 162W
Active power loss / for rated value of the current / at
AC / in hot operating state / per pole
54W
Latching - endurance 15000
Electrical endurance (switching cycles) / at AC-1 / at
380/415 V 50/60 Hz
4000
Neutral conductors / upgradeable/retrofittable Yes
3VA2463-6JP32-0AD0 Subject to change without notice
Page 1/
6
09/14/2019 © Copyright Siemens